Inspection Detail
Inspection: 307430462 - First Electric Cooperative Corporation
Inspection Information - Office: Little Rock Area Office
Site Address:
First Electric Cooperative Corporation
Off Of Myers Farm Rd
Scott, AR 72142
Mailing Address:
1000 S. J.P. Wright Loop Road, Jacksonville, AR 72076
Union Status: NonUnion
SIC:4911
NAICS: 221122/Electric Power Distribution
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 07/07/2004
Emphasis:
Case Closed: 09/27/2004
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100262724 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 5 | 5 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $15,750 | $0 | $0 | $0 | $0 | $15,750 |
| Current Penalty | $7,000 | $0 | $0 | $0 | $0 | $7,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100269 A02 III | 07/19/2004 | 09/02/2004 | $3,500 | $3,500 | $0 | I - Informal Settlement | Citation has been deleted. | |
| 2. | 01002 | Serious | 19100269 B01 I | 07/19/2004 | 09/02/2004 | $1,750 | $1,750 | $0 | I - Informal Settlement | Citation has been deleted. | |
| 3. | 01003 | Serious | 19100269 C01 | 07/19/2004 | 08/12/2004 | $3,500 | $3,500 | $0 | I - Informal Settlement | Citation has been deleted. | |
| 4. | 01004 | Serious | 19100269 M03 V | 07/19/2004 | 07/29/2004 | $3,500 | $3,500 | $0 | I - Informal Settlement | Citation has been deleted. | |
| 5. | 01005 | Serious | 19100269 N02 | 07/19/2004 | 08/05/2004 | $3,500 | $3,500 | $0 | I - Informal Settlement | Citation has been deleted. | |
| 6. | 01006A | Serious | 19100269 A02 III | 07/19/2004 | 09/02/2004 | $3,500 | $0 | $0 | Q - National Office Adjustment | ||
| 7. | 01006B | Serious | 19100269 C01 | 07/19/2004 | 08/12/2004 | $0 | $0 | $0 | Q - National Office Adjustment | ||
| 8. | 01007A | Serious | 19100269 M03 V | 07/19/2004 | 07/29/2004 | $3,500 | $0 | $0 | Q - National Office Adjustment | ||
| 9. | 01007B | Serious | 19100269 N02 | 07/19/2004 | 08/05/2004 | $0 | $0 | $0 | Q - National Office Adjustment |
Investigation Summary
Three power line workers, part of a maintenance crew, were repairing a downed overhead power line. The power line had been damaged during a storm when a tree limb fell on it. Earlier in the day, another crew had pulled the phase conductor back into place, leaving the neutral conductor on the ground. The second crew was to finish the job. The power line was deenergized, and the line was open at a point away from the damaged area. As the three workers took slack out of the primary conductor, using a rope that all three crewmembers were holding, one of them was electrocuted. The crew had not tested the line for voltage or placed grounds on the line before working on it.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LOCKOUT, E PTD, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 307430462 | Fatality | Electric Shock | Occupation not reported |
Translate