Powered by GoogleTranslate

Inspection Detail

Inspection: 307197145 - Global Electric/Communication

Inspection Information - Office: Dosh Seattle Service Location, Seattle, Wa

 

Inspection Nr: 307197145
Report ID: 1055320
Date Opened: 02/01/2004

Site Address:
Global Electric/Communication
24602 Pacific Highway So.
Kent, WA 98030

Mailing Address:
718 47th Street E, Auburn, WA 98092

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 02/12/2004

Emphasis: L:Euc

Case Closed: 10/01/2006


Related Activity
Type Activity Nr Safety Health
Accident 101197143
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 1 2 7
Current Violations 4 1 2 7
Initial Penalty $4,750 $0 $2,000 $100 $0 $6,850
Current Penalty $4,750 $0 $2,000 $100 $0 $6,850
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Repeat 80014005 04/19/2004 05/02/2004 $2,000 $2,000 $0 -  
2. 02001 Serious 80016010 04/19/2004 04/23/2004 $750 $750 $0 -  
3. 02002 Serious 0240096002 04/19/2004 04/23/2004 $1,000 $1,000 $0 -  
4. 02003 Serious 80016040 04/19/2004 04/23/2004 $2,000 $2,000 $0 -  
5. 02004 Serious 0240098004 B 08 04/19/2004 04/23/2004 $1,000 $1,000 $0 -  
6. 03001 Other 8001302501 04/19/2004 04/23/2004 $0 $0 $0 -  
7. 03002 Other 80032005 04/19/2004 04/23/2004 $100 $100 $0 -  

Investigation Summary

Investigation Nr: 202363776
Event: 01/20/2004
Two employees burned by electric arcs from same panel

On Jannuary 20, 2004, Employees #1 and #2, of Global Electric Communications, were installing a new three-phase run of wire in an energized 480-volt panel at a cabinet shop in Kent, WA. Employee #1 was trying to bolt a bracket to the panel's busbar when an electric arc occurred. He sustained thermal burns and was taken to Harborview Burn Center in Seattle, WA. Employee #2 was trying to show the owner of the cabinet shop what had happened to Employee #1 when another electric arc occurred. He also suffered thermal burns and was transported to the same hospital as Employee #1. The arc that burned Employee #1 was caused by a high fault current created by the bracket, of which Employee #1 had lost control. The bracket became energized and contacted another phase in the circuit breaker. Employee #2 thought the panel had been de-energized by the circuit protection at the source.

Keywords: BURN, ELECTRIC ARC, INSTALLING, WORK RULES, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRIC CONDUCTOR, ELECTRICAL BOX, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307197145 Hospitalized injury Burn/Scald(Heat) Occupation not reported
2 307197145 Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close