Powered by GoogleTranslate

Inspection Detail

Inspection: 307166470 - Daniel Electric Company

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 307166470
Report ID: 0950642
Date Opened: 09/23/2005

Site Address:
Daniel Electric Company
3820 East Union Pacific Avenue
Los Angeles, CA 90040

Mailing Address:
1668 West 11th Street, Suite B, Los Angeles, CA 90015

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/09/2005

Planning Guide: Safety-Construction

Emphasis: S:Construction (Cship)

Case Closed: 10/13/2006


Related Activity
Type Activity Nr Safety Health
Accident 101058386
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2 4
Current Violations 2 2 4
Initial Penalty $18,900 $0 $0 $700 $0 $19,600
Current Penalty $10,890 $0 $0 $100 $0 $10,990
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 1509 A 11/04/2005 12/07/2005 $50 $350 $0 I - Informal Settlement  
2. 01002 Other 1509 B 11/04/2005 12/07/2005 $50 $350 $0 I - Informal Settlement  
3. 02001 Serious 23200001 A 11/04/2005 11/14/2005 $90 $5,400 $0 I - Informal Settlement  
4. 03001 Serious 23200002 A 11/04/2005 11/14/2005 $10,800 $13,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 202451514
Event: 09/15/2005
Two employees burned by arc flash from busbars

On September 15, 2005, Employees #1 and #2, of Daniel Electric, were installing circuit breakers on the main electrical panel at a 99 Cents Only store, a chain with which the employer, a licensed electrical contractor, had a long-time business relationship. Employee #1 was holding a screwdriver with one hand and a breaker with the other hand, while Employee #2 held a flashlight and watched from a few feet away. Employee #1 lost his grip on the breaker and it fell across two energized busbars, creating an arc flash that knocked both employees to the ground. The nominal phase-to-phase voltage on the panel was 277 volts, and the phase-to-ground voltage was 480 volts. Employees #1 and #2 were transported USC Medical Center, where Employee #1 was hospitalized and Employee #2 was treated and released. Neither of them had been equipped with approved personal protective equipment, such as face shields, insulated gloves, or insulated tools. The employer was cited for a violation, serious, for not providing and ensuring the use of approved insulated gloves, insulated tools, and eye protection, and for not providing instructions on work techniques and hazards involved in working on energized equipment.

Keywords: ELEC PROTECT EQUIP, ELECTRIC ARC, INSTALLING, WORK RULES, ELECTRICIAN, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRIC SHOCK, ELECTRICAL CABINET, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 307166470 Hospitalized injury Burn/Scald(Heat) Electricians
2 307166470 Non Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close