Inspection Detail
Inspection: 307052217 - Mj Enterprises Electrical Contractors Of Ct, Llc
Inspection Information - Office: Bridgeport Area Office
Site Address:
Mj Enterprises Electrical Contractors Of Ct, Llc
609 W. Johnson Ave.
Cheshire, CT 06410
Mailing Address:
199 Park Rd., Ext., P.O. Box 339, Middlebury, CT 06762
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/25/2004
Emphasis:
Case Closed: 06/29/2004
Type | Activity Nr | Safety | Health |
---|---|---|---|
Referral | 201527942 | Yes |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
Current Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100332 B01 | 05/27/2004 | 06/16/2004 | $1,500 | $1,500 | $0 | - | ||
2. | 01002 | Serious | 19100333 A01 | 05/27/2004 | 06/03/2004 | $1,500 | $1,500 | $0 | - |
Investigation Summary
An electrician was replacing a 480-volt, 100-ampere circuit breaker in an electrical cabinet for a elevator. The buses in the cabinet were energized. He was using a 1/4-in. driver and a flathead screwdriver to install the mounting screws on the left side of the circuit breaker. After placing the circuit breaker into position, he put a screw in the driver and inserted it into the opening in the bottom of the circuit breaker to secure it to the cabinet. He then used the screwdriver in the opening for one of the phases to get the screw started. As the electrician was pushing the screwdriver through the plastic phase guard, it contacted the adjacent phase busbar, causing a phase-to-phase electrical fault. The ensuing electric arc burned the employee on his hands and arms. He was hospitalized for his injuries.
Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, CIRCUIT BREAKER, ELECTRICAL FAULT, HAND TOOL
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 307052217 | Hospitalized injury | Burn/Scald(Heat) | Electricians |