Powered by GoogleTranslate

Inspection Detail

Inspection: 306950833 - Public Service Company Of New Hampshire

Inspection Information - Office: Concord Area Office

 

Inspection Nr: 306950833
Report ID: 0111700
Date Opened: 05/11/2005

Site Address:
Public Service Company Of New Hampshire
Brook St Sub-Station, Canal St, Manchester, Nh
Manchester, NH 03101

Mailing Address:
P.O. Box 330, Manchester, NH 03105

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/05/2005

Emphasis:

Case Closed: 11/23/2005


Related Activity
Type Activity Nr Safety Health
Referral 200617421 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $4,500 $0 $0 $0 $0 $4,500
Current Penalty $4,500 $0 $0 $0 $0 $4,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260028 A 10/18/2005 12/31/2005 $4,500 $4,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200612000
Event: 05/10/2005
Employee Is Burned by Electrical Arc Blast

At approximately 11:47 a.m. on May 10, 2005, two employees of a power company were disconnecting and moving a Westinghouse grounding breaker from a 13.8-kilovolt cabinet. The ground leads had just been disconnected using a "hot-line-tool" (shotgun grounding stick). Employee #1 moved closer to the cabinet, as his coworker turned and moved away to get a T wrench. An arc flash occurred, burning Employee #1's face and hands, and Employee #1 was hospitalized. Employee #1 was wearing a hard hat, safety glasses, fire retardant clothing with hood, and safety boots, but he was not wearing a face shield or gloves. The coworker wore the same personal protective equipment, in addition to a face shield and Class II gloves and leathers.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, PPE, ELEC UTILITY WORK, ELECTRICAL CABINET, ELECTRICAL FAULT, FACE, HAND

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 306950833 Hospitalized injury Burn/Scald(Heat) Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close