Inspection Detail
Inspection: 306844010 - Dynalectric Company
Inspection Information - Office: Department Of Labor, Licensing, And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health
Site Address:
Dynalectric Company
Old Mill Education Center, 600 Patriot Lane
Millersville, MD 21108
Mailing Address:
3601 Commerce Drive, Suite 108, Baltimore, MD 21227
Union Status: Union
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/27/2003
Emphasis: S:Construction, S:Electrocution
Case Closed: 08/31/2004
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 102355328 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 4 | ||||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $16,600 | $0 | $0 | $0 | $0 | $16,600 |
| Current Penalty | $2,075 | $0 | $0 | $2,075 | $0 | $4,150 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 19260021 B02 | 11/24/2003 | 12/27/2003 | $2,075 | $4,150 | $0 | 12/09/2003 | F - Formal Settlement | |
| 2. | 02001 | Serious | 19260416 A01 | 11/24/2003 | 11/28/2003 | $0 | $4,150 | $0 | 12/09/2003 | F - Formal Settlement | Citation has been deleted. |
| 3. | 02002 | Serious | 19260416 A03 | 11/24/2003 | 11/28/2003 | $0 | $4,150 | $0 | 12/09/2003 | F - Formal Settlement | Citation has been deleted. |
| 4. | 02003 | Serious | 19260417 B | 11/24/2003 | 11/28/2003 | $2,075 | $4,150 | $0 | 12/09/2003 | F - Formal Settlement |
Investigation Summary
At approximately 11:40 a.m. on October 1, 2003, Employee #1, a journeyman electrician, was preparing to change the lugs inside a three-phase, 208 volt circuit panel box by moving the three feeder cables out of the way. He was holding two of the cables, one in each hand, when he suffered an electric shock. Employee #1 was transported to Bayview Burn Center, where he was hospitalized overnight. Subsequent investigation found that before the work was started, the employer did not determine whether it was safe for employees to be working in close proximity to live circuits. In addition, the circuit was not verified, by observation or with instruments, to be de-eneegized; the circuit was not de-energized and rendered inoperative; and the circuit was not tagged. It was also determined that the employees needed training in energy control procedures.
Keywords: CLEARANCE, ELEC PROTECT EQUIP, WORK RULES, ELECTRICIAN, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRIC SHOCK, UNTRAINED
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 306844010 | Hospitalized injury | Electric Shock | Electricians |
Translate