Inspection Detail
Inspection: 306839101 - Sumter Utilities
Inspection Information - Office: Sc Department Of Labor, Licensing, And Regulation
Site Address:
Sumter Utilities
Bacon Hill Road
Pinewood, SC 29125
Mailing Address:
Po Box 579, Sumter, SC 29151
Union Status: NonUnion
SIC:1623
NAICS: 237130/Power and Communication Line and Related Structures Construction
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/13/2004
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 09/28/2004
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 100374669 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 1 | 1 | 2 | |||
Initial Penalty | $7,125 | $0 | $0 | $0 | $0 | $7,125 |
Current Penalty | $2,000 | $0 | $0 | $0 | $0 | $2,000 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 19260453 B02 V | 02/25/2004 | 03/01/2004 | $0 | $2,125 | $0 | 03/12/2004 | F - Formal Settlement | |
2. | 01002 | Serious | 19260950 C01 | 02/25/2004 | 03/01/2004 | $2,000 | $5,000 | $0 | 03/12/2004 | F - Formal Settlement |
Investigation Summary
At approximately 11:30 a.m. on January 31, 2004, Employee #1, a lineman, was part of a four-man crew repairing power lines that had been damaged by an ice storm. The crew began work on a pole next to a private drive off a main road. Employee #1 went up in an aerial bucket to replace a missing crossarm on the de-energized pole. He and a coworker then drove to another pole, where they met the other two crew members. Employee #1 was elevated in the bucket to attach a come-along to a downed, de-energized overhead power line, which he was then going to splice and connect to the other part of the line that had fallen to the ground. After connecting the come-along, he began to reposition the bucket to disconnect a stinger line above one of the cut-out switches on the "take off" pole. As Employee #1 moved higher, his right shoulder contacted the stinger line and his left upper arm, creating a path to ground for 7,200 volts. Employee #1 was electrocuted. He was wearing his hard hat but the remainder of his personal protective equipment was on the floor of the bucket. Employee #1 thought the power lines below the cut-out switches were de-energized because the switches were in the OPEN position.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, POWER LINE WORKER, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, ELEC CIRC PART--MISC, ELEC UTILITY WORK
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 306839101 | Fatality | Electric Shock | Electrical power installers and repairers |