Powered by GoogleTranslate

Inspection Detail

Inspection: 306565938 - Seco Industrial Maintenance And Controls

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 306565938
Report ID: 0626600
Date Opened: 10/27/2003

Site Address:
Seco Industrial Maintenance And Controls
14506 Smith Road
Humble, TX 77396

Mailing Address:
1015 West 34th Street, Houston, TX 77018

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/13/2004

Emphasis:

Case Closed: 10/15/2004


Related Activity
Type Activity Nr Safety Health
Accident 101762078
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations 3 3
Initial Penalty $4,500 $0 $0 $0 $0 $4,500
Current Penalty $3,350 $0 $0 $0 $0 $3,350
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A 02/27/2004 03/31/2004 $1,500 $1,500 $0 03/11/2004 F - Formal Settlement  
2. 01002 Serious 19100333 B02 I 02/27/2004 03/02/2004 $350 $1,500 $0 03/11/2004 F - Formal Settlement  
3. 01003 Serious 19100333 B02 IVB 02/27/2004 03/02/2004 $1,500 $1,500 $0 03/11/2004 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201761947
Event: 10/24/2003
Employee electrocuted replacing part in pump feeder box

On October 24, 2003, Employee #1, an electrician, was replacing a CT part in a wastewater pump feeder box. He contacted 4,160 volt energized parts and was electrocuted. The feeder box had fluctuating amps, and the stabs did not separate when the handles were activated. Employee #1 also did not verify the feeder box was de-energized or that the stabs had separated before beginning work.

Keywords: ELECTRICAL, WORK RULES, ELECTRICIAN, ELECTROCUTED, CONSTRUCTION, ELEC CIRC PART--MISC, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 306565938 Fatality Electric Shock Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close