Powered by GoogleTranslate

Inspection Detail

Inspection: 305790362 - General Electrical Systems, Inc.

Inspection Information - Office: Albany Area Office

 

Inspection Nr: 305790362
Report ID: 0213100
Date Opened: 08/26/2003

Site Address:
General Electrical Systems, Inc.
Columbia High School
East Greenbush, NY 12061

Mailing Address:
138 Sicker Rd. P.O. Box 1226, Latham, NY 12110

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Complaint

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/26/2003

Emphasis: L:Fall, S:Construction

Case Closed: 01/28/2004


Related Activity
Type Activity Nr Safety Health
Complaint 203950373 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,500 $0 $0 $0 $0 $2,500
Current Penalty $2,500 $0 $0 $0 $0 $2,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260416 A01 09/08/2003 09/11/2003 $2,500 $2,500 $0 -  
2. 01001B Serious 19260416 A03 09/08/2003 09/11/2003 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 200741403
Event: 08/21/2003
Employee Is Burned in Arc Flash at Panel Box

On August 21, 2003, Employee #1, an electrician, was moving a single leg of an energized 277-volt cable from an energized 480-volt, 300-amp service panel box. The cable was connected to the panel's busbars, causing an arc flash. Employee #1 was hospitalized with second-degree burns on his face and right leg, and third-degree burns on his right arm. A secondary power disconnect was located approximately 4 ft. away from where he was working. Employee #1 failed to follow the company's lockout and tagout procedures.

Keywords: BURN, ELECTRIC ARC, WORK RULES, BUSBAR, CONSTRUCTION, LOCKOUT, ELEC CIRC PART--MISC, ELECTRIC SHOCK, ELECTRICAL BOX, FACE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 305790362 Hospitalized injury Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.