Inspection Detail
Inspection: 305599508 - Dillard Smith Construction Company
Inspection Information - Office: Tennessee Osha Knoxville Office - Safety
Site Address:
Dillard Smith Construction Company
Highway 25w,Pole 56,In Front Of Conoco Station
Lafollette, TN 37766
Mailing Address:
P.O. Box 339, New Market, TN 37820
Union Status: Union
SIC:1623
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/03/2002
Planning Guide: Safety-Construction
Emphasis:
Case Closed: 12/09/2002
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100622018 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $7,000 | $0 | $0 | $0 | $0 | $7,000 |
| Current Penalty | $6,300 | $0 | $0 | $0 | $0 | $6,300 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260950 C01 | 10/15/2002 | 11/17/2002 | $6,300 | $7,000 | $0 | A - Amendment |
Investigation Summary
A power line worker was in a Hi-Ranger aerial lift, clipping in a new overhead power line. He had not covered an existing 7200-volt overhead power line nor was he wearing rubber insulating gloves. The uninsulated section of the boom contacted the energized line while the employee was touching the new, grounded line. The employee was electrocuted when he reached behind his back and contacted the boom or controls.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, BOOM, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 305599508 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate