Inspection Detail
Inspection: 305478174 - Us Construction
Inspection Information - Office: Long Beach District Office
Site Address:
Us Construction
15440 Beach Bl
Westminster, CA 92683
Mailing Address:
2204 Charlotte Ave, Rosemead, CA 91770
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/13/2005
Planning Guide: Safety-Construction
Emphasis: S:Construction (Cship)
Case Closed: 07/19/2007
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362467441 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 2 | 3 | |||
| Current Violations | 1 | 1 | 2 | |||
| Initial Penalty | $13,500 | $0 | $0 | $5,250 | $0 | $18,750 |
| Current Penalty | $2,000 | $0 | $0 | $175 | $0 | $2,175 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 1509 A | 06/20/2005 | 07/08/2005 | $175 | $250 | $0 | 07/11/2005 | L - State Settlement | |
| 2. | 01002 | Other | 342 A | 06/20/2005 | 06/23/2005 | $0 | $5,000 | $0 | 07/11/2005 | L - State Settlement | Citation has been deleted. |
| 3. | 02001 | Serious | 23200004 A02 | 06/20/2005 | 07/08/2005 | $2,000 | $13,500 | $0 | 07/11/2005 | L - State Settlement |
Investigation Summary
An electrician was installing wiring for recessed overhead fluorescent lighting fixtures in the seafood section of a large grocery store under construction. He was using an Upright brand scissor lift (Model No. MX 19; Serial No. 37236) to access the 2.7-meter-high ceiling over the display tanks. The employee was working by the indirect light of the night lighting arrangement, in which every other row of overhead lights was off, including the row he was working on. At approximately 10:00 a.m., a grocery store employee began turning on all of the store lights for the day. When he threw the switch for the seafood area, the electrician received an electric shock and fell 1.5 to 1.8 meters to the floor. He was transported to a hospital for treatment, where he was admitted that day at 11:18 a.m. and released the next day at 4:46 p.m. The electrician had not locked out the switch for the 277-volt circuit on which he was working. The panelboard with the switch was around a corner and behind a wall, where the grocery store employee could not see the electrician working.
Keywords: LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELECTRIC SHOCK, FALL, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 305478174 | Hospitalized injury | Electric Shock | Electricians |
Translate