Inspection: 305476723 - Richard L Schuetze Inc Dba Bolt Electric

Inspection Information - Office: Long Beach District Office

 

Inspection Nr: 305476723
Report ID: 0950635
Date Opened: 08/12/2004

Site Address:
Richard L Schuetze Inc Dba Bolt Electric
2350 W 16 St
Long Beach, CA 90813

Mailing Address:
P O Box 92396, Long Beach, CA 90809

Union Status: NonUnion

SIC:1731

NAICS: 238210/Electrical Contractors


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/10/2004

Emphasis: S:Construction (Cship)

Case Closed: 09/04/2006


Related Activity
Type Activity Nr Safety Health
Accident 362406704
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $0 $0 $0 $335 $0 $335
Current Penalty $0 $0 $0 $335 $0 $335
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citation Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 23200003 09/13/2004 09/16/2004 $335 $335 $0 -  

Investigation Summary

Investigation Nr: 201036068
Event: 04/13/2004
Employee burned by electric arc from circuit panel

At 2:30 p.m. on April 13, 2004, Employee #1, a supervisor for an electrical contractor, was part of a group of workers at a former manufacturing plant that was being converted to a scrap yard by its new owner. Employee #1 and an electrician coworker shut off the 600-amp main breaker, catalog no. QSF 6053T/S2983A17, of a Sylvania electrical panel fed by a 120/240/208 Delta high leg so they could decide whether to modernize or replace the panel. Employee #1 then tried to remove a branch circuit breaker. He was using a screwdriver as a wedge to break the contact clips on the back of the circuit breaker from the busbars when an electrical arc occurred. Employee #1 sustained second-degree burns over 6 percent of his skin surface area that included portions of his head, neck, upper arms, and shoulders. At the time of the accident, he was wearing safety glasses and a short sleeve uniform, but no gloves or hard hat. The screwdriver apparently contacted a busbar behind the breaker, which was energized because one or more poles apparently did not pull free from their contact clips when the breaker was shut off.

Keywords: BURN, ELECTRIC ARC, HEAD, STRUCK AGAINST, BUSBAR, CONSTRUCTION, CIRCUIT BREAKER, ELEC CIRC PART--MISC, HAND TOOL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 305476723 Hospitalized injury Burn/Scald(Heat) Supervisors; electricians & power transm. install.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.