Inspection Detail
Inspection: 305476723 - Richard L Schuetze Inc Dba Bolt Electric
Inspection Information - Office: Long Beach District Office
Site Address:
Richard L Schuetze Inc Dba Bolt Electric
2350 W 16 St
Long Beach, CA 90813
Mailing Address:
P O Box 92396, Long Beach, CA 90809
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/10/2004
Emphasis: S:Construction (Cship)
Case Closed: 09/04/2006
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362406704 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $335 | $0 | $335 |
| Current Penalty | $0 | $0 | $0 | $335 | $0 | $335 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 23200003 | 09/13/2004 | 09/16/2004 | $335 | $335 | $0 | - |
Investigation Summary
At 2:30 p.m. on April 13, 2004, Employee #1, a supervisor for an electrical contractor, was part of a group of workers at a former manufacturing plant that was being converted to a scrap yard by its new owner. Employee #1 and an electrician coworker shut off the 600-amp main breaker, catalog no. QSF 6053T/S2983A17, of a Sylvania electrical panel fed by a 120/240/208 Delta high leg so they could decide whether to modernize or replace the panel. Employee #1 then tried to remove a branch circuit breaker. He was using a screwdriver as a wedge to break the contact clips on the back of the circuit breaker from the busbars when an electrical arc occurred. Employee #1 sustained second-degree burns over 6 percent of his skin surface area that included portions of his head, neck, upper arms, and shoulders. At the time of the accident, he was wearing safety glasses and a short sleeve uniform, but no gloves or hard hat. The screwdriver apparently contacted a busbar behind the breaker, which was energized because one or more poles apparently did not pull free from their contact clips when the breaker was shut off.
Keywords: BURN, ELECTRIC ARC, HEAD, STRUCK AGAINST, BUSBAR, CONSTRUCTION, CIRCUIT BREAKER, ELEC CIRC PART--MISC, HAND TOOL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 305476723 | Hospitalized injury | Burn/Scald(Heat) | Supervisors; electricians & power transm. install. |