Inspection Detail
Inspection: 305471914 - K And B Electric
Inspection Information - Office: Long Beach District Office
Site Address:
K And B Electric
1340 S Sanderson
Anaheim, CA 92806
Mailing Address:
3201 W Warner Ave, Santa Ana, CA 92704
Union Status: NonUnion
SIC:1731
NAICS: 238210/Electrical Contractors
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 05/21/2003
Planning Guide: Safety-Construction
Emphasis: S:Construction (Cship)
Case Closed: 09/04/2006
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 362031635 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | ||||
Current Violations | 2 | 2 | ||||
Initial Penalty | $0 | $0 | $0 | $900 | $0 | $900 |
Current Penalty | $0 | $0 | $0 | $900 | $0 | $900 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Other | 342 A | 05/22/2003 | 05/28/2003 | $225 | $225 | $0 | - | ||
2. | 01002 | Other | 23200002 A03 | 05/22/2003 | 05/28/2003 | $675 | $675 | $0 | - |
Investigation Summary
Two electricians working for an electrical contractor were assigned to install an 800-ampere circuit breaker for a new transformer in a 6.1-meter by 2.4-meter electrical room of a hotel and conference center. The electrical room was located on the side of the complex and opened to the outdoors. After they installed the circuit breaker, the employees reenergized the 480-volt panelboard. Only then did they realize that the grounding lug had not been attached. They believed that they could safely attach the lug while the panelboard was energized. One of the electricians, lying in a prone position, began installing the lug. The wrench he was using hit the busbar causing an electrical fault. The ensuing electric arc burned him. The other electrician, who had left the room before the fault occurred, saw the flash and responded to the accident. The injured employee was hospitalized for one week with second-degree burns to his arms, neck, and face.
Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, PANELBOARD, ELECTRICAL WORK, LOCKOUT, ELECTRICAL FAULT
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 305471914 | Hospitalized injury | Burn/Scald(Heat) | Electricians |