Powered by GoogleTranslate

Inspection Detail

Inspection: 305466245 - K & B Plastics

Inspection Information - Office: Dallas Area Office

 

Inspection Nr: 305466245
Report ID: 0626300
Date Opened: 05/29/2003

Site Address:
K & B Plastics
800 E Wilkinson Dr
Troup, TX 75789

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:3089

NAICS: 326199/All Other Plastics Product Manufacturing


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/29/2003

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 05/17/2006


Related Activity
Type Activity Nr Safety Health
Accident 100782705
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 5 5
Initial Penalty $8,800 $0 $0 $0 $0 $8,800
Current Penalty $300 $0 $0 $0 $0 $300
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100303 C 11/18/2003 01/07/2004 $300 $1,400 $0 12/10/2003 F - Formal Settlement  
2. 01001B Serious 19100303 G02 I 11/18/2003 01/07/2004 $0 $0 $0 12/10/2003 F - Formal Settlement  
3. 01002 Serious 19100304 F05 IVF 11/18/2003 01/07/2004 $0 $2,000 $0 12/10/2003 F - Formal Settlement  
4. 01003A Serious 19100305 B01 11/18/2003 01/07/2004 $0 $1,400 $0 12/10/2003 F - Formal Settlement  
5. 01003B Serious 19100305 G01 I 11/18/2003 01/07/2004 $0 $0 $0 12/10/2003 F - Formal Settlement  
6. 01004A Serious 19100332 B01 11/18/2003 01/07/2004 $0 $2,000 $0 12/10/2003 F - Formal Settlement  
7. 01004B Serious 19100332 B02 11/18/2003 01/07/2004 $0 $0 $0 12/10/2003 F - Formal Settlement  
8. 01005A Serious 19100333 B02 11/18/2003 01/07/2004 $0 $2,000 $0 12/10/2003 F - Formal Settlement  
9. 01005B Serious 19100333 C02 11/18/2003 01/07/2004 $0 $0 $0 12/10/2003 F - Formal Settlement  
10. 01005C Serious 19100333 B02 VA 11/18/2003 01/07/2004 $0 $0 $0 12/10/2003 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200782746
Event: 05/27/2003
Employee Is Electrocuted by Ungrounded Pump

On May 27, 2003, Employee #1 was electrocuted when he contacted the energized metal entrance to a metal building. A worker had wired a water pump motor to an electrical circuit by wrapping the three hot leads with black electrical tape. Two of the leads were not wrapped completely and did not cover the energized wires. The grounding wire was not connected and was not bolted to the frame of the motor. The motor was sitting on concrete, next to the metal building. When motor operated, it rocked and the energized wires made contact with the metal building, which energized the entrance that Employee #1 contacted.

Keywords: SHOCK, ELECTROCUTED, ELECTRIC CONDUCTOR, ELECTRIC SHOCK, PUMP, DOOR, METAL SIDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 305466245 Fatality Electric Shock Misc. metal & plastic processing machine operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.