Inspection Detail
Inspection: 3053949 - City Of New Bern Electrical Services Department
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
City Of New Bern Electrical Services Department
3219 Oaks Rd
New Bern, NC 28560
Mailing Address:
P O Box 1129, New Bern, NC 28560
Union Status: NonUnion
SIC:4911
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: StateGovt
Safety/Health: Safety
Close Conference: 08/11/1986
Emphasis:
Case Closed: 12/31/1989
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360769020 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260400 C01 | 10/20/1986 | 11/24/1986 | $0 | $0 | $0 | - |
Investigation Summary
A WORKER AND HIS FOREMAN RESPONDED TO A SERVICE CALL AT A RESIDENCE TO CHECK A COMPLAINT OF LOW VOLTAGE. UPON ARRIVING AT THE RESIDENCE, THE WORKER ENTERED AN AERIAL LIFT (A LINESMAN II, HI-RANGER MODEL 5FI 48PBI, SERIAL NO. 128011214, MOUNTED ON A CHEVROLET 7000 TRUCK). THE INSULATED LIFT HAD BEEN TESTED 2 MONTHS EARLIER AT 345 KILOVOLTS. THE EMPLOYEE POSITIONED HIMSELF IN THE AERIAL LIFT BUCKET BESIDE THE SECONDARY LINES ON THE UTILITY POLE. HE DETERMINED THAT THE VOLTAGE DROP WAS DUE TO A BAD SERVICE CONNECTION, POSSIBLY CAUSED BY CORRODED AND DIRTY CONDUCTORS AT THE CONNECTION. THE THREE CONDUCTORS OF THE 120-VOLT-TO-GROUND SERVICE DROP WERE DISCONNECTED AND CLEANED. THE EMPLOYEE HAD RECONNECTED TWO OF THE THREE CONDUCTORS AND WAS IN THE PROCESS OF CONNECTING THE THIRD WHEN ONE OF THE TWO RECONNECTED CONDUCTORS CONTACTED THE LEFT SIDE OF HIS BODY WHILE HE WAS HOLDING THE THIRD ONE. THE FOREMAN LOOKED UP, NOTICED THE EMPLOYEE SHAKING, AND LOWERED THE AERIAL LIFT. THE RESUCE SQUAD WAS CALLED AND RESPONDED TO THE SCENE WITHIN TWO MINUTES. THE RESCUE SQUAD BEGAN CARDIO-PULMONARY RESUSCITATION IMMEDIATELY, BUT THE EMPLOYEE WAS DEAD ON ARRIVAL AT THE HOSPITAL. HE HAD BEEN ELECTROCUTED.
Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, CPR, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 3053949 | Fatality | Electric Shock | Electrical power installers and repairers |
Translate