Powered by GoogleTranslate

Inspection Detail

Inspection: 305223273 - Premier Electric

Inspection Information - Office: Tampa Area Office

 

Inspection Nr: 305223273
Report ID: 0420600
Date Opened: 03/08/2002

Site Address:
Premier Electric
4220 Tarpon Avenue
Bonita Springs, FL 34134

Mailing Address:
1443 Rail Head Blvd., Naples, FL 34110

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/30/2002

Emphasis: L:Flcare, S:Construction, S:Construction Fatalities

Case Closed: 05/07/2003


Related Activity
Type Activity Nr Safety Health
Accident 102350238
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $6,575 $0 $0 $0 $0 $6,575
Current Penalty $3,288 $0 $0 $0 $0 $3,288
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260403 H 08/30/2002 09/12/2002 $488 $975 $0 09/20/2002 F - Formal Settlement  
2. 01002A Serious 19260416 A03 08/30/2002 09/12/2002 $2,800 $5,600 $0 09/20/2002 F - Formal Settlement  
3. 01002B Serious 19260417 A 08/30/2002 09/12/2002 $0 $0 $0 09/20/2002 -  

Investigation Summary

Investigation Nr: 202327706
Event: 03/08/2002
Employee electrocuted installing new relay switch

On March 8, 2002, Employee #1, a helper, and an electrician/foreman arrived at a residential construction site to complete the installation of a pump start relay. The work required a new 220-volt line to be pulled from the existing electrical panel over to the junction box that contained the pump start relay. The foreman was doing some work at the truck when Employee #1 removed the cover from the junction box and started to insert a fish tape through the conduit in preparation for pulling the new wires. The fish tape contacted an exposed and energized 120-volt wire from a timer that was also located inside the junction box. Employee #1 received an electric shock and fell to the ground, unresponsive. Coworkers at the job site administered CPR until the Fire Department arrived. Employee #1 was transported to the hospital, where he was pronounced dead. The exposed wires located in the junction box were not tested to determine if they were live, and the electrical circuit for the timer was not turned off, and then locked out or tagged out, at the disconnect switch at the electrical panel.

Keywords: INSTALLING, CPR, WORK RULES, ELECTROCUTED, STRUCK AGAINST, CONSTRUCTION, LOCKOUT, INEXPERIENCE, ELEC CIRC PART--MISC, ELECTRICAL BOX

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 305223273 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.