Powered by GoogleTranslate

Inspection Detail

Inspection: 305032450 - Westar Energy

Inspection Information - Office: Wichita Area Office

 

Inspection Nr: 305032450
Report ID: 0729700
Date Opened: 12/05/2002

Site Address:
Westar Energy
Washington & Mt. Vernon
Wichita, KS 67209

Mailing Address:
P.O. Box 889, Topeka, KS 66601

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 01/22/2003

Emphasis:

Case Closed: 07/30/2004


Related Activity
Type Activity Nr Safety Health
Accident 101342525
Referral 201342813 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3
Current Violations
Initial Penalty $15,000 $0 $0 $0 $0 $15,000
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 A01 03/14/2003 03/26/2003 $0 $5,000 $0 04/04/2003 J - ALJ Decision Citation has been deleted.
2. 01002 Serious 19100333 C02 03/14/2003 03/26/2003 $5,000 $5,000 $0 04/04/2003 J - ALJ Decision Citation has been deleted.
3. 01003 Serious 19100269 L02 03/14/2003 03/26/2003 $0 $5,000 $0 04/04/2003 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 201342623
Event: 12/04/2002
ELECTRIC SHOCK - DIRECT CONTACT WITH ENERGIZED PARTS

A power line crew was at a construction site to facilitate a planned outage for the removal five sets of cables from a 7200/480-volt pad-mounted transformer. While they were working, the employees noticed a blown lightning arrester on one phase on the primary side of the transformer. After they completed their assigned tasks, the employees decided to move the blown arrester to prevent contact of the arrester cap with the transformer frame. One of the employees contacted an energized part on the live-front primary side of the transformer. He was electrocuted.

Keywords: ELEC PROTECT EQUIP, LIGHTNING ARRESTER, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC CIRC PART--MISC, ELEC UTILITY WORK, TRANSFORMER

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 305032450 Fatality Electric Shock Electricians' apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close