Powered by GoogleTranslate

Inspection Detail

Inspection: 304756885 - Consolidated Engineering Services

Inspection Information - Office: Baltimore Area Office

 

Inspection Nr: 304756885
Report ID: 0316100
Date Opened: 01/14/2002

Site Address:
Consolidated Engineering Services
2201 C Street, Nw
Washington, DC 20006

Mailing Address:
2345 Crystal Drive, Arlington, VA 22202

Union Status: NonUnion

SIC:8711

NAICS: 541330/Engineering Services


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/12/2002

Emphasis:

Case Closed: 02/12/2002


Related Activity
Type Activity Nr Safety Health
Accident 102040284

Investigation Summary

Investigation Nr: 202023248
Event: 01/08/2002
Burn - Electrical Fault in Motor Starter

An electrical worker working alone was performing scheduled maintenance on a starter motor control unit. He turned the handle on the exterior of the starter motor unit to deenergize the starter motor unit, which left the line side of the unit energized. The employee thought that the line side connection was loose, so he started to tighten it. His screwdriver touched the side of the cover, causing an electrical fault. The ensuing electric arc burned the employee and blew all three phase conductors off their connections, and some component melting occurred. The injured employee was able to reach a phone, which was approximately 4.5 meters from the work area, and telephoned for help. Emergency medical services flushed the injured employee's face with water and transported him to a burn unit. Doctors treated the injured worker for burns to his entire face, neck and right hand, but he died from these injuries 4 days after the accident.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL CABINET, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 304756885 Fatality Electric Shock Electronic repairers, communica. & indus. equip.
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.