Powered by GoogleTranslate

Inspection Detail

Inspection: 304630635 - Phoenix Electric, Inc.

Inspection Information - Office: Atlanta East Area Office

 

Inspection Nr: 304630635
Report ID: 0418100
Date Opened: 05/23/2002

Site Address:
Phoenix Electric, Inc.
4350 George Town Square
Atlanta, GA 30374

Mailing Address:
139 New Hope Road, Suite A, Lawrenceville, GA 30045

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/24/2002

Emphasis: S:Construction Fatalities

Case Closed: 11/16/2002


Related Activity
Type Activity Nr Safety Health
Accident 101281590
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 1 1 2
Initial Penalty $4,900 $0 $0 $2,500 $0 $7,400
Current Penalty $4,900 $0 $0 $100 $0 $5,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A01 09/11/2002 10/07/2002 $4,900 $4,900 $0 -  
2. 02001 Other 19040039 A 09/11/2002 09/16/2002 $100 $2,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201281342
Event: 05/10/2002
Employee electrocuted while replacing a light fixture

On May 10, 2002, Employee #1 was replacing a 277-volt, 2-by-4 ceiling light fixture. He removed the lens cover and then the ballast canopy, which was located on the inside of the fixture. This exposed the ballast and the associated wiring for the feeder whip and lamp ends. Next, Employee #1 removed the whip plate from the back of the light fixture, which was still energized. He used wire strippers held in his right hand to cut the ballast wire at the same time as his left arm was touching the grounded ceiling grid and his left hand was holding the light fixture. The current passed through his body from where the energized spring on the wire strippers was touching his hand to the contact points with his left arm and hand. Employee #1 was electrocuted.

Keywords: LIGHTING CIRCUIT, INSULATED TOOL, WORK RULES, ELECTROCUTED, LIGHTING FIXTURE, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC, ARM

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 304630635 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.