Site Address:
Westerm Us Lighting & Electric
Merrill Engineering U Of U
Salt Lake City, UT 84112

Mailing Address:
380 W 1700 S, Slc, UT 84115

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/06/2001

Planning Guide: Safety-Construction

Emphasis: S:Construction, S:Construction Fatalities

Case Closed: 12/31/2002


Related Activity
Type Activity Nr Safety Health
Accident 362654220
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 3 6
Current Violations 3 1 4
Initial Penalty $3,600 $0 $0 $1,250 $0 $4,850
Current Penalty $3,600 $0 $0 $250 $0 $3,850
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100333 C02 01/08/2002 01/14/2002 $1,200 $1,200 $0 -  
2. 01002 Serious 19100335 A02 I 01/08/2002 01/14/2002 $1,200 $1,200 $0 -  
3. 01003 Serious 19100335 A02 II 01/08/2002 01/14/2002 $1,200 $1,200 $0 -  
4. 02001 Other 10005 C02 01/08/2002 01/14/2002 $500 $500 $0 A - Amendment Citation has been deleted.
5. 02002 Other 10005 C06 01/08/2002 01/14/2002 $500 $500 $0 A - Amendment Citation has been deleted.
6. 02003 Other 10008 C01 01/08/2002 01/14/2002 $250 $250 $0 -  

Investigation Summary

Investigation Nr: 171061401
Event: 09/07/2001
Three employees burned by arc from electrical panel

On September 7, 2001, Employees #1 through #3, all electricians, were installing a new disconnect in the main electrical panel of the Merrill Engineering Building on the University of Utah campus. Employee #1 was using a hand wrench to tighten the lug on the grounding cable, Employee #2 was holding a flashlight for him, and Employee #3 was holding the conductors. As they were working, Employee #1's wrench contacted a 480-volt buss, resulting in an electrical arc to ground (277-volts buss to ground). All three workers suffered severe electrical flash burns and were hospitalized. They had been using uninsulated tools and had not paid attention to a missing guard in the electrical panel, which allowed contact with an energized buss.

Keywords: BURN, ELEC PROTECT EQUIP, ELECTRIC ARC, WORK RULES, ELECTRICIAN, STRUCK AGAINST, BUSBAR, CONSTRUCTION, ELECTRICAL WORK, HAND TOOL

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 304411531 Hospitalized injury Electric Shock Electricians' apprentices
2 304411531 Hospitalized injury Burn/Scald(Heat) Electricians' apprentices
3 304411531 Hospitalized injury Burn/Scald(Heat) Electricians' apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.