Inspection Detail
Inspection: 304086788 - Bogot Services, Inc
Inspection Information - Office: Chicago South Area Office
Site Address:
Bogot Services, Inc
900 N. Lake Shore Drive
Chicago, IL 60611
Mailing Address:
730 N. Busse Highway, Park Ridge, IL 60068
Union Status: Union
SIC:1711
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 02/07/2002
Emphasis:
Case Closed: 04/04/2002
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100031236 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $5,000 | $0 | $0 | $0 | $0 | $5,000 |
| Current Penalty | $4,000 | $0 | $0 | $0 | $0 | $4,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19100333 B02 I | 02/21/2002 | 04/12/2002 | $2,000 | $2,500 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19100335 A02 I | 02/21/2002 | 03/26/2002 | $2,000 | $2,500 | $0 | I - Informal Settlement |
Investigation Summary
At 10:15 a.m. on August 31, 2001, Employee #1 arrived at a building in Chicago where he was to perform a regularly scheduled preventive maintenance check on the chiller units. Upon his arrival, the building engineer informed him that the #3 fan motor was not working and gave him access to the chiller fans. At approximately 4:00 p.m., a janitor found Employee #1, dead, lying between two fan motors. The disconnect for the #3 fan motor was open. The junction box below the #4 fan motor disconnect was also open and the wires coming from it had been cut. A pair of wire cutters with burn marks on the handle were found next to Employee #1, who also had burn marks on his right hand. The equipment being worked on had not been locked out.
Keywords: BURN, MAINTENANCE, REPAIR, ELECTRICAL, WORK RULES, ELECTROCUTED, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 304086788 | Fatality | Electric Shock | Occupation not reported |
Translate