Inspection Detail
Inspection: 303991137 - Genuine Parts Company
Inspection Information - Office: Jacksonville Area Office
Site Address:
Genuine Parts Company
10629 Atlantic Boulevard
Jacksonville, FL 32225
Mailing Address:
1090 Haines Street, Jacksonville, FL 32206
Union Status: NonUnion
SIC:5531
NAICS: 441310/Automotive Parts and Accessories Stores
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Health
Close Conference: 04/04/2003
Emphasis:
Case Closed: 06/12/2003
Type | Activity Nr | Safety | Health |
---|---|---|---|
Accident | 101352821 |
Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
---|---|---|---|---|---|---|
Initial Violations | 2 | 2 | 4 | |||
Current Violations | 2 | 2 | 4 | |||
Initial Penalty | $1,700 | $0 | $0 | $0 | $0 | $1,700 |
Current Penalty | $1,700 | $0 | $0 | $0 | $0 | $1,700 |
FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
# | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
---|---|---|---|---|---|---|---|---|---|---|---|
1. | 01001 | Serious | 19100037 A03 | 05/12/2003 | 05/15/2003 | $0 | $0 | $0 | - | ||
2. | 01002 | Serious | 19100151 C | 05/12/2003 | 05/15/2003 | $1,700 | $1,700 | $0 | - | ||
3. | 02001 | Other | 19100305 G01 III | 05/12/2003 | 05/15/2003 | $0 | $0 | $0 | - | ||
4. | 02002 | Other | 19100305 G02 II | 05/12/2003 | 05/15/2003 | $0 | $0 | $0 | - |
Investigation Summary
Employee #1 died of Pneumonia. The death certificate listed Employee #1's cause of death as Legionnaire's disease. During the inspection, samples were collected from all possible water sources at the work place. A sample of the hot water from the women's bathroom had 60 colony forming units per milliliter of Legionella pneumophila serogroup 1 on the culture. A sample of hot water from the men's bathroom had 20 colony forming units per milliliter of a mixed plate of Legionella pneumophila serogroup 1and Legionella dumoffii on the culture. Both samples were initial flush samples, and the water temperature was around 118 degrees Fahrenheit. These levels were approaching levels of Legionella bacteria that may cause an outbreak of diseases, such as Legionnaire's disease and Pontiac Fever. No other water samples had indications of the bacteria being present, and no current employees had been diagnosed as having the disease. Unfortunately, no samples from the deceased were kept by the hospital, and a genetic comparison could not be made to determine if the same bacteria was involved. Hence, it could not be proved that the disease was work related.
Keywords: LEGIONNAIRES DISEASE
# | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
---|---|---|---|---|---|---|
1 | 303991137 | Fatality | Other | Sales counter clerks |