Powered by GoogleTranslate

Inspection Detail

Inspection: 303845374 - South Fork Electric, Inc.

Inspection Information - Office: Nc Department Of Labor - Winston-Salem

 

Inspection Nr: 303845374
Report ID: 0453720
Date Opened: 02/01/2001

Site Address:
South Fork Electric, Inc.
799 Highland Ave
Winston-Salem, NC 27101

Mailing Address:
3909-B Country Club Rd., Winston-Salem, NC 27104

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 04/04/2001

Planning Guide: Safety-Construction

Emphasis: S:Program Improvements

Case Closed: 12/03/2001


Related Activity
Type Activity Nr Safety Health
Accident 100071158
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $2,100 $0 $0 $0 $0 $2,100
Current Penalty $1,680 $0 $0 $0 $0 $1,680
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19260416 A01 04/18/2001 04/23/2001 $1,680 $2,100 $0 I - Informal Settlement  
2. 01001B Serious 19260021 B02 04/18/2001 06/05/2001 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 200071124
Event: 01/31/2001
Electric Shock - Direct Contact with Energized Conductor

An electrician was sitting on the top plate of an interior wall, working within the ceiling space of a suspended ceiling. He was disconnecting conductors for a 277-volt, 16-ampere lighting fixture while the lighting circuit was energized. He turned to his right, placed his right hand on a steel support for the interior wall, and reaching into a 102-millimeter by 102-millimeter electrical box to disconnect the conductors. The employee contacted an energized conductor and was electrocuted.

Keywords: LIGHTING CIRCUIT, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, LIGHTING FIXTURE, ELECTRICAL WORK, LOCKOUT, E C, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303845374 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close