Inspection: 303771661 - Island Electric Company, Inc.

Inspection Information - Office: Savannah Area Office

 

Inspection Nr: 303771661
Report ID: 0418400
Date Opened: 06/03/2002

Site Address:
Island Electric Company, Inc.
106 Gleneagles
St Simons Island, GA 31522

Mailing Address:
94 Riverview Drive, St Simons Island, GA 31522

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 09/12/2002

Planning Guide: Safety-Construction

Emphasis: S:Construction, S:Construction Fatalities

Case Closed: 03/14/2003


Related Activity
Type Activity Nr Safety Health
Accident 100901776
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $5,900 $0 $0 $3,500 $0 $9,400
Current Penalty $3,500 $0 $0 $1,900 $0 $5,400
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260403 H 09/12/2002 10/08/2002 $500 $1,000 $0 I - Informal Settlement  
2. 01002 Serious 19260417 A 09/12/2002 10/30/2002 $3,000 $4,900 $0 I - Informal Settlement  
3. 02001 Other 19040039 A 09/12/2002 09/17/2002 $1,900 $3,500 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200901072
Event: 05/30/2002
Employee electrocuted when lines accidentally energized

On May 30, 2002, Employee #1, an apprentice electrician, and a lead electrician were checking to see if the two junction boxes feeding two pairs of ceiling-mounted lighting fixture boxes in the greatroom of a house were made up and completed. The junction boxes were located in the attic and, upon examination, were found not to have been completed. The lead electrician instructed Employee #1 to do this for both boxes. Prior to starting the job, the lead electrician said they first had to check and make sure that the electricity was cut off to the two junction boxes. He told Employee #1 to wait in the attic until he reached the switches in the greatroom. Once there, they worked together to find and ensure that all the proper switches were turned off. They also verified with a circuit tester that the electrical cables going to the two junction boxes were de-energized. The lead electrician went back to the attic to check on Employee #1 and then returned into the greatroom, where he spoke with an employee of another company. In addition to the lead electrician and his apprentice, there were three other individuals working in and around the house that day, each of which had access to the greatroom where the switches were located. At some point, one or both of the switches to the two junction boxes were re-energized. When the lead electrician completed his conversation, he went back to attic. He found Employee #1 laying over the flexible air conditioning duct located directly in front of the two junction boxes on which he'd been working. The lead electrician ran down from the attic and switched off the two main electrical disconnects to the house. He then called for help and went back up into the attic. When he arrived back in the attic, he pulled Employee #1 away from the air conditioning duct and administered CPR. Employee #1 had been electrocuted. The switches were not locked out or otherwise rendered inoperative, nor were the switches tagged.

Keywords: REPAIR, CPR, WORK RULES, ELECTROCUTED, CONSTRUCTION, LOCKOUT, ELEC CIRC PART--MISC, ELECTRICAL BOX, COMMUNICATION

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303771661 Fatality Electric Shock Electricians' apprentices
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.