Inspection Detail
Inspection: 303733653 - Omaha Boring Inc.
Inspection Information - Office: Omaha Area Office
Site Address:
Omaha Boring Inc.
60th And Sorensen Parkway
Omaha, NE 68106
Mailing Address:
4173 Cass Street, Omaha, NE 68131
Union Status: NonUnion
SIC:1794
NAICS: 0
Inspection Type: Referral
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/27/2002
Planning Guide: Safety-Construction
Emphasis: N:Trench, S:Construction
Case Closed: 10/09/2002
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Referral | 200053551 | Yes |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 1 | 1 | ||||
| Current Violations | 1 | 1 | ||||
| Initial Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| Current Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 19101200 H01 I | 09/30/2002 | 11/01/2002 | $0 | $0 | $0 | - |
Investigation Summary
On September 26, 2002, Employee #1 was working with a VAC unit when, for an unknown reason, a nearby underground electrical line became grounded. The subsequent arc blast caught Employee #1 and threw him backwards. He was stunned but the arc blast didn't directly contact him and he suffered no serious injuries. He was transported to a local hospital, where he was treated and released. Subsequent investigation revealed that Employee #1 was using a Ring0Matic VAC machine to clean the dirt away from a buried power cable. It was manufactured in 2000 and was purchased as previously owned with 258 hours of use. His company had been hired to replace power lines in a substation complex due to the facility being modernized. The VAC unit was being used to accomplish the cleaning in locations known to hold underground utility cables. It uses water at 3,000 psi to break the dirt free and create a slurry which is then vacuumed by the unit. The system is contained on a trailer and contains its own water supply and catch tank. Personnel from the local power company, the owners of the cable, believe that there may have been a defect in the insulation of the cable. This allowed the water from the VAC unit to enter the power cable and create a grounded path, leading to the arc blast.
Keywords: LEAK, ELECTRIC ARC, PROTECTIVE GROUNDING, ELECTRIC CABLE, CLEANING, CAUGHT BY, CONSTRUCTION, UNDRGRD POWER LINE
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 303733653 | Non Hospitalized injury | Other | Occupation not reported |
Translate