Inspection Detail
Inspection: 303679484 - Knight Light, Inc.
Inspection Information - Office: Denver Area Office
Site Address:
Knight Light, Inc.
4601 Dtc Boulevard (Texaco Building)
Denver, CO 80237
Mailing Address:
3260 S. Gilpin Street, Englewood, CO 80110
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Complete
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 03/05/2002
Emphasis: S:Construction Fatalities
Case Closed: 05/29/2003
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 101571982 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 6 | 6 | ||||
| Current Violations | 4 | 2 | 6 | |||
| Initial Penalty | $9,000 | $0 | $0 | $0 | $0 | $9,000 |
| Current Penalty | $6,000 | $0 | $0 | $0 | $0 | $6,000 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260020 B01 | 03/08/2002 | 06/06/2002 | $1,500 | $1,500 | $0 | 04/08/2002 | F - Formal Settlement | |
| 2. | 01002 | Other | 19260021 B02 | 03/08/2002 | 06/06/2002 | $0 | $1,500 | $0 | 04/08/2002 | F - Formal Settlement | |
| 3. | 01003 | Serious | 19260028 A | 03/08/2002 | 06/06/2002 | $1,500 | $1,500 | $0 | 04/08/2002 | F - Formal Settlement | |
| 4. | 01004 | Serious | 19260416 A01 | 03/08/2002 | 06/06/2002 | $1,500 | $1,500 | $0 | 04/08/2002 | F - Formal Settlement | |
| 5. | 01005 | Other | 19260416 A03 | 03/08/2002 | 06/06/2002 | $0 | $1,500 | $0 | 04/08/2002 | F - Formal Settlement | |
| 6. | 01006 | Serious | 19260417 B | 03/08/2002 | 06/06/2002 | $1,500 | $1,500 | $0 | 04/08/2002 | F - Formal Settlement |
Investigation Summary
On September 20, 2001, Employee #1, of Knight Light, Inc., was on the fourth floor of an office building, retrofitting the existing fluorescent light fixtures with energy-efficient ballast units and lamps. The work was being done at night so as not to interfere with normal business hours. At the time of the accident, Employee #1 was working on a light fixture that was not de-energized because it was part of the emergency lighting system. This fixture had been worked on by a less-experienced retrofitter, who had been shocked while servicing it and Employee #1, who had more experience, had come from a nearby location to investigate. He was working alone when he was apparently electrocuted by contact with the same lighting fixture. There were no witnesses to the accident. Apparently, an evaluation of the facility and project scope had been conducted by walking through the building prior to beginning the job. The evaluation of site-specific hazards and development of safe work practices were apparently inadequate. There was no provision for lockout/tagout procedures or devices to ensure that deenergized electrical circuits could not be inadvertently energized while being serviced.
Keywords: LIGHTING CIRCUIT, ELECTRICAL, WORK RULES, ELECTRICIAN, ELECTROCUTED, LIGHTING FIXTURE, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 303679484 | Fatality | Electric Shock | Occupation not reported |
Translate