Inspection: 303679484 - Knight Light, Inc.

Inspection Information - Office: Denver Area Office

 

Inspection Nr: 303679484
Report ID: 0830500
Date Opened: 09/21/2001

Site Address:
Knight Light, Inc.
4601 Dtc Boulevard (Texaco Building)
Denver, CO 80237

Mailing Address:
3260 S. Gilpin Street, Englewood, CO 80110

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 03/05/2002

Emphasis: S:Construction Fatalities

Case Closed: 05/29/2003


Related Activity
Type Activity Nr Safety Health
Accident 101571982
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 6 6
Current Violations 4 2 6
Initial Penalty $9,000 $0 $0 $0 $0 $9,000
Current Penalty $6,000 $0 $0 $0 $0 $6,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260020 B01 03/08/2002 06/06/2002 $1,500 $1,500 $0 04/08/2002 F - Formal Settlement  
2. 01002 Other 19260021 B02 03/08/2002 06/06/2002 $0 $1,500 $0 04/08/2002 F - Formal Settlement  
3. 01003 Serious 19260028 A 03/08/2002 06/06/2002 $1,500 $1,500 $0 04/08/2002 F - Formal Settlement  
4. 01004 Serious 19260416 A01 03/08/2002 06/06/2002 $1,500 $1,500 $0 04/08/2002 F - Formal Settlement  
5. 01005 Other 19260416 A03 03/08/2002 06/06/2002 $0 $1,500 $0 04/08/2002 F - Formal Settlement  
6. 01006 Serious 19260417 B 03/08/2002 06/06/2002 $1,500 $1,500 $0 04/08/2002 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201571064
Event: 09/20/2001
Employee electrocuted by energized light fixture

On September 20, 2001, Employee #1, of Knight Light, Inc., was on the fourth floor of an office building, retrofitting the existing fluorescent light fixtures with energy-efficient ballast units and lamps. The work was being done at night so as not to interfere with normal business hours. At the time of the accident, Employee #1 was working on a light fixture that was not de-energized because it was part of the emergency lighting system. This fixture had been worked on by a less-experienced retrofitter, who had been shocked while servicing it and Employee #1, who had more experience, had come from a nearby location to investigate. He was working alone when he was apparently electrocuted by contact with the same lighting fixture. There were no witnesses to the accident. Apparently, an evaluation of the facility and project scope had been conducted by walking through the building prior to beginning the job. The evaluation of site-specific hazards and development of safe work practices were apparently inadequate. There was no provision for lockout/tagout procedures or devices to ensure that deenergized electrical circuits could not be inadvertently energized while being serviced.

Keywords: LIGHTING CIRCUIT, ELECTRICAL, WORK RULES, ELECTRICIAN, ELECTROCUTED, LIGHTING FIXTURE, CONSTRUCTION, ELECTRICAL WORK, LOCKOUT, ELEC CIRC PART--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303679484 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close