Inspection Detail

Inspection: 303638167 - Oklahoma Gas & Electric

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 303638167
Report ID: 0627700
Date Opened: 08/18/2000

Site Address:
Oklahoma Gas & Electric
321 N. Harvey
Oklahoma City, OK 73101

Mailing Address:
P.O. Box 321, M/C 506, Oklahoma City, OK 73101

Union Status: NonUnion

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/24/2000

Emphasis:

Case Closed: 11/23/2000


Related Activity
Type Activity Nr Safety Health
Accident 100641844
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations
Initial Penalty $18,000 $0 $0 $0 $0 $18,000
Current Penalty $0 $0 $0 $0 $0 $0
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 10/20/2000 10/24/2000 $4,500 $4,500 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19260950 B01 10/20/2000 10/24/2000 $4,500 $4,500 $0 I - Informal Settlement Citation has been deleted.
3. 01003 Serious 19260950 C01 10/20/2000 10/24/2000 $4,500 $4,500 $0 I - Informal Settlement Citation has been deleted.
4. 01004 Serious 19260955 C02 10/20/2000 10/24/2000 $4,500 $4,500 $0 I - Informal Settlement Citation has been deleted.

Investigation Summary

Investigation Nr: 200641454
Event: 08/18/2000
electric shock - direct contact with overhead line

When a two-person power line crew arrived at a work site, the employees noticed that the B-phase of a 7200-volt overhead power line was down. They positioned their aerial lift under the power line near the utility pole supporting the line. Working on the ground, the crew spliced the downed conductor on the east side of the pole. They then pulled the conductor toward the pole. One employee entered the aerial lift bucket and elevated himself into position at the top of the pole. He raised the conductor to the top of the pole; and, as he was pulling on it, he contacted the A-phase conductor located on the north side of the pole. He was electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303638167 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close