Inspection Detail
Inspection: 303258578 - E.I. Dupont Denemours Company, Inc.
Inspection Information - Office: Va-E-Richmond (Regional Office) - Safety 0355111
Site Address:
E.I. Dupont Denemours Company, Inc.
5401 Jefferson Davis Highway
Richmond, VA 23234
Mailing Address:
P.O. Box 27001, Richmond, VA 23261
Union Status: Union
SIC:3275
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 10/08/1999
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 02/07/2000
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100920107 |
Investigation Summary
Four electricians working in a substation had just finished moving some 480-volt circuit breakers from standby cubicles back to the normal position. Two of the employees had gone outside to cool off, and the other two started replacing covers on the unused openings in the standby cubicle doors. The two employees who had gone outside returned to help. As employee #3 walked by one of the doors, he pushed it shut with his foot. The cover plate, which had just been placed on the threaded studs without being secured, fell into the lower energized stabs and caused an electrical fault. The ensuing electric arc burned three of the four employees. They were hospitalized with first-, second-, and third-degree burns.
Keywords: BURN, CLOTHING, E GI II, ELECTRIC ARC, ELECTRICAL, ELECTRICIAN, ELECTRICAL WORK, CIRCUIT BREAKER, ELECTRICAL FAULT, UNSTABLE POSITION
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 303258578 | Hospitalized injury | Burn/Scald(Heat) | Electricians | ||
| 2 | 303258578 | Hospitalized injury | Burn/Scald(Heat) | Electricians | ||
| 3 | 303258578 | Hospitalized injury | Burn/Scald(Heat) | Electricians |