Powered by GoogleTranslate

Inspection Detail

Inspection: 303119036 - The L.E. Myers Co.

Inspection Information - Office: Chicago South Area Office

 

Inspection Nr: 303119036
Report ID: 0521700
Date Opened: 03/25/2000

Site Address:
The L.E. Myers Co.
West Frontage Road
Plainfield, IL 60544

Mailing Address:
2695 Crooks Road, Rochester Hills, MI 48309

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/21/2000

Emphasis: L:Ohpwrlne

Case Closed: 01/26/2006


Related Activity
Type Activity Nr Safety Health
Accident 100030824
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 7 8
Current Violations 1 1 2 4
Initial Penalty $3,500 $560,000 $0 $0 $0 $563,500
Current Penalty $3,500 $42,000 $0 $0 $112,000 $157,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 L06 III 09/22/2000 09/27/2000 $3,500 $3,500 $0 09/26/2000 F - Formal Settlement  
2. 02001 Willful 19100269 A02 I 09/22/2000 09/27/2000 $70,000 $70,000 $0 09/26/2000 F - Formal Settlement Citation has been deleted.
3. 02002A Unclass 19100269 C 09/22/2000 09/28/2000 $56,000 $70,000 $0 09/26/2000 F - Formal Settlement  
4. 02002B Unclass 19100269 C02 I 09/22/2000 09/28/2000 $0 $0 $0 09/26/2000 F - Formal Settlement  
5. 02003A Willful 19100269 L02 09/22/2000 09/27/2000 $70,000 $70,000 $0 09/26/2000 F - Formal Settlement Citation has been deleted.
6. 02003B Willful 19100269 P04 I 09/22/2000 09/27/2000 $0 $0 $0 09/26/2000 F - Formal Settlement Citation has been deleted.
7. 02004 Willful 19100269 N03 09/22/2000 09/27/2000 $42,000 $70,000 $0 09/26/2000 F - Formal Settlement  
8. 02005 Willful 19100269 N03 09/22/2000 09/27/2000 $70,000 $70,000 $0 09/26/2000 F - Formal Settlement Citation has been deleted.
9. 02006 Willful 19100269 N03 09/22/2000 09/27/2000 $70,000 $70,000 $0 09/26/2000 F - Formal Settlement Citation has been deleted.
10. 02007A Unclass 19100269 N03 09/22/2000 09/27/2000 $56,000 $70,000 $0 09/26/2000 F - Formal Settlement  
11. 02007B Unclass 19100269 N03 09/22/2000 09/27/2000 $0 $70,000 $0 09/26/2000 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200030963
Event: 03/25/2000
ELECTRIC SHOCK - CONTACT WITH OVERHEAD LINE THRU GROUND WIRE

A journeyman power line worker and a first-step apprentice were working from an uninsulated aerial lift, replacing bell insulators on a deenergized, three-phase, 345-kilovolt overhead power line. Steel towers supported the line. The crew had grounded the deenergized line, but had not set up an equipotential zone at the tower at which they were working. The power line worker was electrocuted when he contacted an end of an energized protective ground. The apprentice also received an electric shock when the aerial lift platform became energized. He was hospitalized for his injuries.

Keywords: OVERHEAD POWER LINE, PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, INDUCED CURRENT, ELEC UTILITY WORK, ELECTRIC SHOCK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 303119036 Fatality Electric Shock Electrical power installers and repairers
2 303119036 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.