Powered by GoogleTranslate

Inspection Detail

Inspection: 302901962 - Watson Irrigation Specialists, Inc.

Inspection Information - Office: Billings Area Office

 

Inspection Nr: 302901962
Report ID: 0830100
Date Opened: 05/24/2001

Site Address:
Watson Irrigation Specialists, Inc.
7837 Hwy 287
Townsend, MT 59644

Mailing Address:
, , 00000

Union Status: NonUnion

SIC:7699

NAICS: 0 


Inspection Type: Complaint

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/24/2001

Emphasis:

Case Closed: 06/26/2001


Related Activity
Type Activity Nr Safety Health
Complaint 202936498 Yes Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 2 1 3
Initial Penalty $1,950 $0 $0 $0 $0 $1,950
Current Penalty $1,000 $0 $0 $0 $0 $1,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100215 A02 06/08/2001 06/16/2001 $225 $450 $0 I - Informal Settlement  
2. 01001B Serious 19100215 A04 06/08/2001 06/16/2001 $0 $0 $0 -  
3. 01001C Serious 19100215 B01 06/08/2001 06/16/2001 $0 $0 $0 -  
4. 01002 Serious 19100333 A 06/08/2001 07/11/2001 $775 $1,500 $0 I - Informal Settlement  
5. 02001 Other 19100178 L 06/08/2001 07/11/2001 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 201861275
Event: 05/22/2001
Burn - Electrical Fault in Electrical Cabinet

Two employees were connecting a new cabinet for an irrigation pump to a 480-volt service. A grounding conductor ran through the cabinet and lay loose in a gutter above the disconnect. As they were working with the grounding conductors, one employee moved the loose grounding conductor enough that it contacted one of the energized busbars. An electrical fault occurred, and the ensuing electric arc burned the employee. He was hospitalized with first- and second-degree burns.

Keywords: BURN, ELECTRIC ARC, E GI IV, ELECTRICAL, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR, ELECTRICAL CABINET, ELECTRICAL FAULT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302901962 Hospitalized injury Burn/Scald(Heat) Laborers, except construction
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.