Powered by GoogleTranslate

Inspection Detail

Inspection: 302541859 - National Grid

Inspection Information - Office: Concord Area Office

 

Inspection Nr: 302541859
Report ID: 0111700
Date Opened: 04/05/2001

Site Address:
National Grid
Jones Rd
Windham, NH 03087

Mailing Address:
9 Lowell Road, Salem, NH 03079

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Referral

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/10/2001

Emphasis: S:Construction

Case Closed: 10/11/2001


Related Activity
Type Activity Nr Safety Health
Referral 200615177 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $10,000 $0 $0 $0 $0 $10,000
Current Penalty $10,000 $0 $0 $0 $0 $10,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260416 A02 09/18/2001 09/26/2001 $5,000 $5,000 $0 -  
2. 01002 Serious 19260950 B01 09/18/2001 09/28/2001 $5,000 $5,000 $0 -  

Investigation Summary

Investigation Nr: 200610988
Event: 04/05/2001
Shock & Burn - Electrical Fault in Underground Cable

Two employees of a power line contractor were driving a 2.4-meter length of copper ground rod into the ground at a substation. The employees drove the ground rod the first meter or so by hand. They then connected an air hammer to the rod. When the rod reached a depth of about 1.2 meters, it penetrated a concrete-encased 13.2-kilovolt (phase-to-phase) underground cable and caused an electrical fault. The ensuing electric arc burned both employees. Employee # 1 also received an electric shock that resulted in the amputation of his right little finger and three third-degree entry and exit burns on both hands. Employee # 2, who also received an electric shock but let go of the air hammer, sustained burns to his face, ears, hand, and lips. The two employees were hospitalized for their injuries. The employees, who had been wearing safety glasses, hard hats, safety boots, and leather gloves, had not been aware of the buried cable.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, ELECTRICAL FAULT, GROUNDING ELECTRODE, UNDRGRD POWER LINE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302541859 Hospitalized injury Electric Shock Electrical power installers and repairers
2 302541859 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.