Powered by GoogleTranslate

Inspection Detail

Inspection: 302396924 - Cannon Construction, Inc.

Inspection Information - Office: Jackson Area Office

 

Inspection Nr: 302396924
Report ID: 0419400
Date Opened: 07/16/2000

Site Address:
Cannon Construction, Inc.
2118 Summit-Holmesville Road
Mccomb, MS 39648

Mailing Address:
P. O. Box 979, Brookhaven, MS 39602

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/20/2000

Planning Guide: Safety-Construction

Emphasis: S:Construction, S:Construction Fatalities

Case Closed: 12/27/2000


Related Activity
Type Activity Nr Safety Health
Accident 101361806
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 2
Current Violations 2 2
Initial Penalty $11,500 $0 $0 $0 $0 $11,500
Current Penalty $8,500 $0 $0 $0 $0 $8,500
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 5A0001 12/12/2000 01/09/2001 $3,300 $4,500 $0 I - Informal Settlement  
2. 01002 Serious 19260950 C01 12/12/2000 12/18/2000 $5,200 $7,000 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201361300
Event: 07/11/2000
Electric Shock - Direct Contact with Energized Parts

An employee working from an aerial lift was replacing an insulator at substation. The employee, who was not wearing flame-resistant clothing, was wearing rubber insulating gloves but not rubber insulating sleeves. His arm contacted a disconnect switch, and he received an electric shock passing from arm to arm. The employee's shirt ignited. Other employees lowered the injured employee to the ground, removed him from the bucket, and extinguished his burning shirt. The employee was electrocuted.

Keywords: CLOTHING, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRIC SWITCH, POWER LINE WORKER, INSULATOR, ELECTROCUTED, E PTD, SUBSTATION, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302396924 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.