Inspection Detail
Inspection: 302390091 - Temco Electric, Inc.
Inspection Information - Office: Oklahoma City Area Office
Site Address:
Temco Electric, Inc.
7633 E 63rd Place
Tulsa, OK 74133
Mailing Address:
5903 East 11th Street, Tulsa, OK 74112
Union Status: NonUnion
SIC:1731
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: Y
Ownership: Private
Safety/Health: Safety
Close Conference: 06/14/2000
Emphasis: S:Construction Fatalities
Case Closed: 03/02/2001
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100641760 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 1 | 5 | |||
| Current Violations | 4 | 1 | 5 | |||
| Initial Penalty | $12,000 | $0 | $0 | $5,000 | $0 | $17,000 |
| Current Penalty | $5,400 | $0 | $0 | $2,000 | $0 | $7,400 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Serious | 19260028 A | 08/03/2000 | 08/07/2000 | $1,800 | $3,000 | $0 | I - Informal Settlement | ||
| 2. | 01002 | Serious | 19260416 A01 | 08/03/2000 | 08/07/2000 | $1,800 | $3,000 | $0 | I - Informal Settlement | ||
| 3. | 01003 | Serious | 19260416 A03 | 08/03/2000 | 08/07/2000 | $0 | $3,000 | $0 | I - Informal Settlement | ||
| 4. | 01004 | Serious | 19260417 C | 08/03/2000 | 08/07/2000 | $1,800 | $3,000 | $0 | I - Informal Settlement | ||
| 5. | 02001 | Other | 19040008 | 08/03/2000 | 08/08/2000 | $2,000 | $5,000 | $0 | I - Informal Settlement |
Investigation Summary
A journeyman electrician and an apprentice were working on an interior finish construction project, removing 277-volt fluorescent lighting fixtures and replacing them with a string of temporary lights. The two employees were working in separate rooms. A junction box was in the ceiling above the wall that divided the two rooms. The panelboard containing the circuit breakers controlling the lighting circuits was 18.3 meters away and was not visible to the apprentice. The pair had been turning the circuits off and on. The apprentice electrician was standing on a 1.8-meter fiberglass ladder, holding a pair of 230-millimeter electrician's pliers. He apparently cut through an energized conductor while he was touching the steel ceiling grid. (The ceiling grid and the pliers each had a burn mark.) The apprentice was electrocuted.
Keywords: LIGHTING CIRCUIT, ELECTRICAL, INSULATED TOOL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, E C
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 302390091 | Fatality | Electric Shock | Electricians' apprentices |
Translate