Powered by GoogleTranslate

Inspection Detail

Inspection: 302383518 - Metro Pump Llc

Inspection Information - Office: Oklahoma City Area Office

 

Inspection Nr: 302383518
Report ID: 0627700
Date Opened: 05/13/1999

Site Address:
Metro Pump Llc
10203 N. Cinncinati
Sperry, OK 74073

Mailing Address:
15301 E 15th Street, Jones, OK 73049

Union Status: NonUnion

SIC:1799

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 05/14/1999

Emphasis: S:Construction Fatalities

Case Closed: 08/19/1999


Related Activity
Type Activity Nr Safety Health
Accident 361823057
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 2 5
Current Violations 2 1 2 5
Initial Penalty $2,800 $0 $4,000 $0 $0 $6,800
Current Penalty $2,800 $0 $4,000 $0 $0 $6,800
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100134 C01 08/04/1999 08/22/1999 $2,000 $2,000 $0 -  
2. 01002A Serious 19260651 K01 08/04/1999 08/09/1999 $800 $800 $0 -  
3. 01002B Serious 19260652 A01 08/03/1999 08/06/1999 $0 $0 $0 -  
4. 02001 Repeat 19100307 B 08/04/1999 08/08/1999 $4,000 $4,000 $0 -  
5. 03001 Other 19101200 E01 I 08/04/1999 08/22/1999 $0 $0 $0 -  
6. 03002 Other 19101200 G01 08/04/1999 08/22/1999 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 200640233
Event: 05/12/1999
Employee killed when gasoline tank explodes

Employees #1 and #2 were in a 4 ft deep excavation at a construction site, removing, replacing, and resealing the leaking manhole cover from an underground 8,000-gallon gasoline tank. They had removed several bolts and nuts holding the cover in place, but were having difficulty removing the remaining fasteners. Employee #1 used an electric right-angle grinder borrowed from the station owner to remove two of the remaining bolts and nuts. According to Employee #2, Employee #1 had pushed the hot bolts into the tank. As Employee #1 was grinding the third bolt, there was an explosion in the tank. Employee #1 was thrown 228 ft from the top of the tank and was killed. Employee #2 sustained injuries, but did not require hospitalization. They were using a Venturi air blower to remove vapors from the gasoline tank, but Employee #1 was using an electric grinder that was inappropriate for this task and that, according to his coworker, was generating a lot of sparks. The explosion was most likely caused by sparks and/or the hot bolts igniting explosive vapors in the tank.

Keywords: GRINDER, REPAIR, VAPOR, FLAMMABLE VAPORS, WORK RULES, CONSTRUCTION, GAS, EXPLOSION, SPARK, TANK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302383518 Fatality Other Occupation not reported
2 302383518 Non Hospitalized injury Burn/Scald(Heat) Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close