Inspection Detail
Inspection: 302335260 - Electric Metering Corporation
Inspection Information - Office: Allentown Area Office
Site Address:
Electric Metering Corporation
202 William Leigh Drive
Tullytown, PA 19007
Mailing Address:
202 William Leigh Drive, Tullytown, PA 19007
Union Status: NonUnion
SIC:3612
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Health
Close Conference: 06/27/2000
Emphasis:
Case Closed: 01/02/2002
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 101320091 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 2 | 2 | ||||
| Current Violations | 2 | 2 | ||||
| Initial Penalty | $3,000 | $0 | $0 | $0 | $0 | $3,000 |
| Current Penalty | $2,250 | $0 | $0 | $0 | $0 | $2,250 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001A | Serious | 19100132 D01 | 06/29/2000 | 07/17/2000 | $1,125 | $1,500 | $0 | I - Informal Settlement | ||
| 2. | 01001B | Serious | 19100335 A01 I | 06/29/2000 | 07/17/2000 | $0 | $0 | $0 | - | ||
| 3. | 01002 | Serious | 19100303 G02 I | 06/29/2000 | 07/17/2000 | $1,125 | $1,500 | $0 | I - Informal Settlement |
Investigation Summary
An employee was testing a potential transformer, Model PT145, manufactured by the employer (Electric Metering Corporation). The testing procedure called for connecting several leads with alligator clips from a Falcon voltage tester to the potential transformer and then energizing the transformer with a 480-volt power supply. The employee apparently contacted a lead while it was energized and was electrocuted. The insulation on the leads was intact, and each alligator clips had rubber covering everything except the tip, which was bare metal. The employee was not using rubber insulating gloves and was standing on a concrete floor. The autopsy revealed electrical burns on the left index finger and on the middle of the palm on the right hand.
Keywords: E GI II, ELEC PROTECT EQUIP, ELECTRICAL, ELECTRICAL TESTING, ELECTROCUTED, ELEC CIRC PART--MISC
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 302335260 | Fatality | Electric Shock | Occupation not reported |
Translate