Powered by GoogleTranslate

Inspection Detail

Inspection: 302316088 - Brink Electric Construction Co.

Inspection Information - Office: Englewood Area Office

 

Inspection Nr: 302316088
Report ID: 0830600
Date Opened: 05/19/2000

Site Address:
Brink Electric Construction Co.
1800 South Abilene
Aurora, CO 80011

Mailing Address:
P.O. Box 1186, Rapid City, SD 57709

Union Status: NonUnion

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/20/2000

Emphasis: S:Construction Fatalities

Case Closed: 07/28/2000


Related Activity
Type Activity Nr Safety Health
Accident 101750883
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 3 3
Initial Penalty $38,000 $0 $0 $0 $0 $38,000
Current Penalty $22,000 $0 $0 $0 $0 $22,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260950 B01 07/05/2000 07/10/2000 $7,000 $7,000 $0 I - Informal Settlement Citation has been deleted.
2. 01002 Serious 19260950 B02 07/05/2000 07/10/2000 $7,000 $7,000 $0 I - Informal Settlement Citation has been deleted.
3. 01003 Serious 19260950 D01 IV 07/05/2000 07/10/2000 $7,000 $7,000 $0 I - Informal Settlement  
4. 01004 Serious 19260952 B02 07/05/2000 07/10/2000 $5,000 $7,000 $0 I - Informal Settlement  
5. 01005A Serious 19260950 B01 07/05/2000 07/10/2000 $10,000 $10,000 $0 -  
6. 01005B Serious 19260950 B02 07/05/2000 07/10/2000 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 201750486
Event: 05/18/2000
electric shock - direct contact with energized parts

A power line worker working in a substation was replacing a jumper on a deenergized conductor. Protective grounds had not been installed, and the jumper was energized by induced current. The employee was electrocuted.

Keywords: PROTECTIVE GROUNDING, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, SUBSTATION, INDUCED CURRENT, ELEC UTILITY WORK, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302316088 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close