Powered by GoogleTranslate

Inspection Detail

Inspection: 302273594 - Potomac Electric Power Company

Inspection Information - Office: Department Of Labor, Licensing And Regulation Division Of Labor And Industry Maryland Occupational Safety And Health

 

Inspection Nr: 302273594
Report ID: 0352460
Date Opened: 09/08/1998

Site Address:
Potomac Electric Power Company
Morgantown Generating Station, 12620 Crain Highway
Newburg, MD 20664

Mailing Address:
1900 Pennsylvania Avenue Nw, Washington, DC 20068

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/17/1998

Emphasis:

Case Closed: 06/22/1999


Related Activity
Type Activity Nr Safety Health
Accident 100964287
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1 2
Current Violations 2 2
Initial Penalty $3,600 $0 $0 $3,600 $0 $7,200
Current Penalty $0 $0 $0 $7,200 $0 $7,200
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19100335 A01 I 10/20/1998 10/22/1998 $3,600 $3,600 $0 F - Formal Settlement  
2. 01002 Other 19100335 A01 V 10/20/1998 10/22/1998 $3,600 $3,600 $0 F - Formal Settlement  

Investigation Summary

Investigation Nr: 200962322
Event: 09/08/1998
BURN - ELECTRICAL FAULT IN CIRCUIT BREAKER

A fuel and ash technician was in a coal yard breaker house working on an ITE K600 480-volt, 300-ampere circuit breaker. As the employee was racking the circuit breaker back in, an electrical fault occurred. He sustained second- and third-degree burns to his right arm, shoulders, back, neck, and face. He was hospitalized for his injuries. His employer required a switching jacket, ultra-violet-rated face shield, gloves with leather protectors, and rubber insulating sleeves. However, the employee was not wearing the proper personal protective equipment.

Keywords: BURN, CLOTHING, ELECTRIC ARC, ELECTRICAL, PPE, E PTD, CIRCUIT BREAKER, ELEC UTILITY WORK, ELECTRICAL FAULT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302273594 Hospitalized injury Burn/Scald(Heat) Miscellaneous plant and system operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.