Powered by GoogleTranslate

Inspection Detail

Inspection: 302126719 - Ionni Sign Company

Inspection Information - Office: Parsippany Area Office

 

Inspection Nr: 302126719
Report ID: 0214200
Date Opened: 05/14/1998

Site Address:
Ionni Sign Company
Dover Dairy Maid, Route No. 46
Dover, NJ 07801

Mailing Address:
114 Beach Street, Bldg. No. 3, Rockaway, NJ 07866

Union Status: NonUnion

SIC:7312

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 11/09/1998

Emphasis:

Case Closed: 01/02/2001


Related Activity
Type Activity Nr Safety Health
Accident 100020551
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 14 14
Current Violations 14 14
Initial Penalty $18,450 $0 $0 $0 $0 $18,450
Current Penalty $8,303 $0 $0 $0 $0 $8,303
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100303 B01 11/09/1998 11/30/1998 $270 $600 $0 I - Informal Settlement  
2. 01002 Serious 19100303 C 11/09/1998 12/07/1998 $270 $600 $0 I - Informal Settlement  
3. 01003 Serious 19100303 F 11/09/1998 11/20/1998 $203 $450 $0 I - Informal Settlement  
4. 01004 Serious 19100304 F04 11/09/1998 11/16/1998 $945 $2,100 $0 I - Informal Settlement  
5. 01005 Serious 19100304 F05 IVB 11/09/1998 11/20/1998 $945 $2,100 $0 I - Informal Settlement  
6. 01006 Serious 19100305 A01 I 11/09/1998 11/30/1998 $270 $600 $0 I - Informal Settlement  
7. 01007 Serious 19100305 B01 11/09/1998 11/20/1998 $203 $450 $0 I - Informal Settlement  
8. 01008 Serious 19100305 E01 11/09/1998 11/20/1998 $202 $450 $0 I - Informal Settlement  
9. 01009 Serious 19100305 J01 IV 11/09/1998 12/29/1998 $270 $600 $0 I - Informal Settlement  
10. 01010 Serious 19100306 A01 11/09/1998 11/18/1998 $945 $2,100 $0 I - Informal Settlement  
11. 01011 Serious 19100332 B01 11/09/1998 12/29/1998 $945 $2,100 $0 I - Informal Settlement  
12. 01012 Serious 19100333 A01 11/09/1998 11/13/1998 $945 $2,100 $0 I - Informal Settlement  
13. 01013 Serious 19100333 C02 11/09/1998 11/20/1998 $945 $2,100 $0 I - Informal Settlement  
14. 01014 Serious 19100335 A01 I 11/09/1998 11/16/1998 $945 $2,100 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 200021160
Event: 05/13/1998
ELECTRIC SHOCK - GROUND FAULT IN ELECTRIC SIGN

Two employees were servicing a large illuminated sign. They changed the fluorescent bulbs, but the sign still did not light. They found that some conductors had burned through the wire nuts connecting them. The employees changed three conductors, but the sign still did not light. One of the employees went to the back of the sign to turn it off. There was not much room between the angle iron on the sign and the air conditioning ductwork. He was electrocuted when he contacted the sign or angle iron and the air conditioning duct at the same time. Two years earlier, the same two employees had raised the sign, extending the wiring and adding a junction box when they did so. However, they did not connect the equipment grounding conductor at the box. An apparent ground fault in the sign had energized its frame and the angle iron supporting it.

Keywords: E GI III, ELECTRICAL, ELECTRIC SIGN, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, GROUND FAULT, EQUIPMENT GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302126719 Fatality Electric Shock Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.