Powered by GoogleTranslate

Inspection Detail

Inspection: 302013354 - Orange County Remc

Inspection Information - Office: Indiana Department Of Labor

 

Inspection Nr: 302013354
Report ID: 0551800
Date Opened: 03/16/2001

Site Address:
Orange County Remc
7133 North State Road 337
Orleans, IN 47452

Mailing Address:
P.O. Box 208, Orleans, IN 47452

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 06/26/2001

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 08/13/2001


Related Activity
Type Activity Nr Safety Health
Accident 362662652
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 1 6
Current Violations 5 1 6
Initial Penalty $7,500 $0 $0 $0 $0 $7,500
Current Penalty $3,750 $0 $0 $0 $0 $3,750
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100269 A02 IVA 07/13/2001 07/19/2001 $750 $1,500 $0 I - Informal Settlement  
2. 01002 Serious 19100269 L02 I 07/13/2001 07/19/2001 $750 $1,500 $0 I - Informal Settlement  
3. 01003 Serious 19100269 L02 II 07/13/2001 07/19/2001 $750 $1,500 $0 I - Informal Settlement  
4. 01004 Serious 19100269 L04 07/13/2001 07/19/2001 $750 $1,500 $0 I - Informal Settlement  
5. 01005 Serious 19100269 M03 II 07/13/2001 07/19/2001 $750 $1,500 $0 I - Informal Settlement  
6. 02001 Other 4000402 07/13/2001 07/18/2001 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 170388755
Event: 03/13/2001
Electric Shock - Direct Contact with Overhead Line

Two power line workers were assigned to repair a conductor on a utility pole. The conductor had been damaged by a storm. They arrived at the worksite, which was near a residence, in an aerial lift truck. They decided to climb the pole rather than damage the soft ground with the truck. One of the power line workers climbed the pole and removed a jumper that connected a tap conductor to an overhead feed-through conductor. With his right foot on the pole ground, the employee reached toward the pole to adjust the conductor sag at the dead-end clamp. He was not wearing rubber insulating gloves at the time. He contacted the overhead feed-through conductor with his left hand and received an electric shock. The other power line worker, who was on the ground to check the sag of the tap conductor, heard an arcing sound and turned to see his coworker slumped against the pole, supported by his body belt. The employee on the ground summoned emergency medical services as he rescued his coworker in the aerial lift. The injured power line worker was hospitalized.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 302013354 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close