Powered by GoogleTranslate

Inspection Detail

Inspection: 301815171 - Philip Morris Products, Inc.

Inspection Information - Office: Va-E-Richmond (Regional Office) - Safety 0355111

 

Inspection Nr: 301815171
Report ID: 0355111
Date Opened: 09/16/1998

Site Address:
Philip Morris Products, Inc.
20520 Unico Road
Mckenney, VA 23872

Mailing Address:
P.O. Box 120, Mckenney, VA 23872

Union Status: NonUnion

SIC:2141

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 10/19/1998

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 04/29/1999


Related Activity
Type Activity Nr Safety Health
Accident 362315004
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 1
Current Violations 1 1
Initial Penalty $7,000 $0 $0 $0 $0 $7,000
Current Penalty $7,000 $0 $0 $0 $0 $7,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100332 B01 02/11/1999 02/16/1999 $7,000 $7,000 $0 -  
2. 01001B Serious 19100333 A01 02/11/1999 02/16/1999 $0 $0 $0 -  

Investigation Summary

Investigation Nr: 948893
Event: 09/16/1998
ELECTRIC SHOCK - CONTACT WITH LIVE CONDUCTOR THRU FISH TAPE

An electrician was using a 3-millimeter-wide metal fish tape to pull eight No. 14 conductors through a 152-millimeter-square metal electrical duct. The duct enclosed about 75 existing energized conductors. The employee had pulled the new conductors about 9 meters when he encountered some resistance. Electrical tape had been wrapped around five of the existing conductors, and the fish tape got caught on the electrical tape. When the employee tried to free the fish tape, it cut into a 227-volt conductor, and he was electrocuted.

Keywords: METAL WIRE, E GI IV, ELECTRICAL, ELECTRICIAN, ELECTROCUTED, ELECTRICAL WORK, LOCKOUT, ELECTRIC CONDUCTOR

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301815171 Fatality Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.