Inspection Detail
Inspection: 301788758 - Wake Electric Membership Corpporation
Inspection Information - Office: Nc Department Of Labor - Raleigh
Site Address:
Wake Electric Membership Corpporation
414 East Wait Avenue
Wake Forest, NC 27588
Mailing Address:
Pob 1229, Wake Forest, NC 27588
Union Status: NonUnion
SIC:4911
NAICS: 0
Inspection Type: Unprog Rel
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/25/1997
Planning Guide: Safety-Manufacturing
Emphasis:
Case Closed: 09/29/1997
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 100350420 |
Investigation Summary
A power line worker was working from an aerial lift, 4.6 meters above a paved road surface. He was removing an aluminum block suspended from a deenergized conductor. The block had been used to pull a new neutral conductor. The employee positioned the aerial lift bucket between an existing, energized 7200-volt copper overhead power line conductor and one of the new aluminum conductors. The two conductors were about 0.9 to 1.2 meters apart. The energized conductor was behind the employee. The employee had untied the block from the upper cable and had released the neutral cable from the block. As he was lowering the bucket, the existing phase conductor apparently caught on the fall protection attachment on the boom, which was 305 millimeters from the bucket. The conductor pulled taut and snapped back toward the bucket, contacting the employee. The employee apparently fell forward into the neutral. He sustained an electric shock and thermal burns resulting in cardiopulmonary failure. A coworker (a ground worker trainee) initiated emergency procedures and lowered the boom. The other crewmembers removed the injured employee from the bucket and administered cardiopulmonary resuscitation until emergency medical services arrived. The injured employee was hospitalized at a local burn center. However, he never regained consciousness and died of his injuries 22 days after the accident.
Keywords: OVERHEAD POWER LINE, ELECTRICAL, ELECTRIC SHOCK, AERIAL LIFT, BURN, ELEC PROTECT EQUIP, POWER LINE WORKER, E PTD, ELEC UTILITY WORK
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 301788758 | Occupation Not Listed |
Translate