Investigation Summary

Investigation Nr: 200350395
Event: 07/15/1997
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

A power line worker was working from an aerial lift, 4.6 meters above a paved road surface. He was removing an aluminum block suspended from a deenergized conductor. The block had been used to pull a new neutral conductor. The employee positioned the aerial lift bucket between an existing, energized 7200-volt copper overhead power line conductor and one of the new aluminum conductors. The two conductors were about 0.9 to 1.2 meters apart. The energized conductor was behind the employee. The employee had untied the block from the upper cable and had released the neutral cable from the block. As he was lowering the bucket, the existing phase conductor apparently caught on the fall protection attachment on the boom, which was 305 millimeters from the bucket. The conductor pulled taut and snapped back toward the bucket, contacting the employee. The employee apparently fell forward into the neutral. He sustained an electric shock and thermal burns resulting in cardiopulmonary failure. A coworker (a ground worker trainee) initiated emergency procedures and lowered the boom. The other crewmembers removed the injured employee from the bucket and administered cardiopulmonary resuscitation until emergency medical services arrived. The injured employee was hospitalized at a local burn center. However, he never regained consciousness and died of his injuries 22 days after the accident.

Keywords: OVERHEAD POWER LINE, ELECTRICAL, ELECTRIC SHOCK, AERIAL LIFT, BURN, ELEC PROTECT EQUIP, POWER LINE WORKER, E PTD, ELEC UTILITY WORK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301788758 Occupation Not Listed
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.