| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 360262067 |
Investigation Summary
Employees #1 and #2 were applying insulation to the interior of an HVAC duct with a flammable adhesive. The duct did not have mechanical ventilation. Electrical flood-type lamps, electrical extension cords, and a receptacle outlet were in the duct. This equipment was not approved for use in Class I locations. Within the duct work at another location, an employee was spot welding pins in place. The flammable vapors ignited, resulting in a flash fire that burned Employees #1 and #2 over approximately 90 percent of their bodies. They died.
Keywords: BURN, SPOT WELDING, DUCT, VENTILATION, FLAMMABLE VAPORS, WORK RULES, FIRE, CONSTRUCTION, SPARK, ELECTRIC LIGHT--PORT
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 3015484 | Fatality | Burn/Scald(Heat) | Insulation Workers | ||
| 2 | 3015484 | Fatality | Burn/Scald(Heat) | Insulation Workers |