Inspection: 301332326 - So. California Edison

Inspection Information - Office: Monrovia District Office

 

Inspection Nr: 301332326
Report ID: 0950644
Date Opened: 06/16/2004

Site Address:
So. California Edison
1100 N. Grand Ave.
Walnut, CA 91789

Mailing Address:
14660 Chestnut St., Westminster, CA 92683

Union Status: Union

SIC:4911

NAICS: 221122/Electric Power Distribution


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/09/2004

Emphasis:

Case Closed: 12/28/2007


Related Activity
Type Activity Nr Safety Health
Accident 362494890
Accident 362495012
Accident 362495111
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 2 1 3
Current Violations 1 2 3
Initial Penalty $45,000 $0 $0 $1,060 $0 $46,060
Current Penalty $18,000 $0 $0 $2,120 $0 $20,120
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 2714 A 12/08/2004 01/05/2005 $1,060 $1,060 $0 07/12/2005 W - Empr Withdrew  
2. 02001 Other 29400002 A 12/08/2004 12/18/2004 $1,060 $22,500 $0 07/12/2005 F - Formal Settlement  
3. 03001 Serious 2943 E 12/08/2004 12/18/2004 $18,000 $22,500 $0 07/12/2005 F - Formal Settlement  

Investigation Summary

Investigation Nr: 201798865
Event: 06/10/2004
Electric Shock - Direct Contact with Energized Conductor

Three meter technicians were installing transformers in new metering switchgear at a cogeneration facility at a college campus. After opening the disconnect on the metering compartments, one of the workers cut the insulation boards at the lower portion of the metering compartment. This operation generated dust, and the worker used a rag to wipe off the boards. As he was wiping the top of the metering compartment, the worker contacted an energized 12-kilovolt conductor. He received an electric shock and sustained burns to his hands. He was hospitalized for his injuries. The door at the upper portion of the metering compartment had not been closed while the employees were working on the switchgear, and the employees had not been using personal protective equipment.

Keywords: BURN, ELEC PROTECT EQUIP, ELECTRICAL, CLEANING, ELECTRICIAN, LOCKOUT, UNGUARDED LIVE PARTS, E PTD, ELEC UTILITY WORK, ELECTRIC SHOCK

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301332326 Hospitalized injury Burn/Scald(Heat) Power plant operators
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.