Powered by GoogleTranslate

Inspection Detail

Inspection: 301313482 - Donohue Industries, Inc.

Inspection Information - Office: Houston North Area Office

 

Inspection Nr: 301313482
Report ID: 0626600
Date Opened: 09/01/1998

Site Address:
Donohue Industries, Inc.
Hwy. 103 East
Lufkin, TX 75902

Mailing Address:
Hwy. 103 East, Lufkin, TX 75902

Union Status: Union

SIC:2621

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: Y

Ownership: Private

Safety/Health: Safety

Close Conference: 09/16/1998

Planning Guide: Safety-Manufacturing

Emphasis:

Case Closed: 01/05/2011


Related Activity
Type Activity Nr Safety Health
Accident 101760429
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 5 5
Current Violations 2 2
Initial Penalty $35,000 $0 $0 $0 $0 $35,000
Current Penalty $14,000 $0 $0 $0 $0 $14,000
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19100254 C02 I 12/10/1998 12/14/1998 $7,000 $7,000 $0 01/05/1999 A - Amendment Citation has been deleted.
2. 01002 Serious 19100334 A03 II 12/10/1998 12/14/1998 $7,000 $7,000 $0 01/05/1999 A - Amendment Citation has been deleted.
3. 01003 Serious 19100334 A04 12/10/1998 12/14/1998 $7,000 $7,000 $0 01/05/1999 A - Amendment Citation has been deleted.
4. 01004A Serious 19100255 C06 12/10/1998 12/14/1998 $7,000 $7,000 $0 01/05/1999 -  
5. 01004B Serious 19100334 A03 II 12/10/1998 12/14/1998 $0 $0 $0 01/05/1999 -  
6. 01005 Serious 19100334 A04 12/10/1998 12/14/1998 $7,000 $7,000 $0 01/05/1999 -  

Investigation Summary

Investigation Nr: 201760709
Event: 08/31/1998
electric shock - ground fault in electric welder

Two employees were spot welding on a drum decker. One of them picked the welding lead up from the ground and was electrocuted. The welding machine was a 480-volt, single-phase machine, and its plug would not fit the 480-volt, three-phase receptacles in the plant. The plant electrician had removed the single-phase plug and replaced it with a three-phase plug, removing the connection for the equipment grounding conductor in the process. Even though the instructions for the welding machine did not recommend using it in wet conditions, the employees were using it under wet conditions. The employees had been working in a hot, wet area; their clothes were wet; and they were wet. Employees interviewed after the accident stated that people had received electric shocks from the machine before the accident.

Keywords: E GI V, ELECTRICAL, ELECTROCUTED, WELDER, ATTACHMENT PLUG, GROUND FAULT, EQUIPMENT GROUNDING

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301313482 Fatality Electric Shock Occupation not reported
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close