Powered by GoogleTranslate

Inspection Detail

Inspection: 301190302 - U.S. Postal Service

Inspection Information - Office: Washington Area Office

 

Inspection Nr: 301190302
Report ID: 1032300
Date Opened: 06/26/2000

Site Address:
U.S. Postal Service
1815 Sw Campus Dr.
Federal Way, WA 98023

Mailing Address:
, , 00000

Union Status: Union

SIC:4311

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 08/01/2000

Emphasis:

Case Closed: 01/16/2001


Related Activity
Type Activity Nr Safety Health
Accident 101580231
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 3 2 5
Current Violations 3 2 5
Initial Penalty $15,750 $0 $0 $0 $0 $15,750
Current Penalty $9,450 $0 $0 $0 $0 $9,450
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001A Serious 19100332 B01 11/16/2000 11/26/2000 $3,150 $3,150 $0 I - Informal Settlement  
2. 01001B Serious 19100333 C02 11/16/2000 11/26/2000 $0 $0 $0 I - Informal Settlement  
3. 01002A Serious 19100333 A01 11/16/2000 11/26/2000 $3,150 $3,150 $0 I - Informal Settlement  
4. 01002B Serious 19100333 B02 11/16/2000 11/26/2000 $0 $0 $0 I - Informal Settlement  
5. 01003A Serious 19100333 B02 IVA 11/16/2000 11/26/2000 $6,300 $6,300 $0 I - Informal Settlement Citation has been deleted.
6. 01003B Serious 19100333 B02 IVB 11/16/2000 11/26/2000 $3,150 $3,150 $0 I - Informal Settlement  
7. 02001 Other 19100303 G01 II 11/16/2000 11/21/2000 $0 $0 $0 I - Informal Settlement  
8. 02002 Other 19100333 B02 I 11/16/2000 11/26/2000 $0 $0 $0 I - Informal Settlement  

Investigation Summary

Investigation Nr: 201580768
Event: 06/26/2000
electric shock - contact with energized parts thru tool

An employee with no electrical or lockout-tagout training had removed a leaking ballast from a 277-volt fluorescent light and was installing a replacement. He had opened the wrong circuit breaker and had not tested the circuit to ensure it was deenergized before he started working on it. He apparently contacted energized part through an uninsulated tool he was using and was electrocuted. He had contact burns on his right hand and left arm.

Keywords: BALLAST--LIGHTING, LIGHTING CIRCUIT, E GI IV, ELECTRICAL, ELECTROCUTED, LIGHTING FIXTURE, ELECTRICAL WORK, LOCKOUT, UNTRAINED

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301190302 Fatality Electric Shock Janitors and cleaners
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.