Inspection: 301023081 - Olson Electric Company Inc.

Inspection Information - Office: Jacksonville Area Office

 

Inspection Nr: 301023081
Report ID: 0419700
Date Opened: 03/11/1998

Site Address:
Olson Electric Company Inc.
Area Of Se 8th Ave & Se 13th Terrace
Starke, FL 32091

Mailing Address:
225 Carswell Avenue, Holly Hill, FL 32117

Union Status: Union

SIC:1731

NAICS: 0 


Inspection Type: Accident

Scope: Complete

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 07/28/1998

Emphasis:

Case Closed: 09/30/1998


Related Activity
Type Activity Nr Safety Health
Accident 361090798
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $15,375 $0 $0 $0 $0 $15,375
Current Penalty $15,375 $0 $0 $0 $0 $15,375
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260453 B03 09/09/1998 10/27/1998 $4,500 $4,500 $0 -  
2. 01002A Serious 19260502 D 09/09/1998 10/27/1998 $1,875 $1,875 $0 -  
3. 01002B Serious 19260502 D15 09/09/1998 10/27/1998 $0 $0 $0 -  
4. 01003 Serious 19260950 C01 09/09/1998 10/27/1998 $4,500 $4,500 $0 -  
5. 01004 Serious 19260950 C02 I 09/09/1998 10/27/1998 $4,500 $4,500 $0 -  

Investigation Summary

Investigation Nr: 201350485
Event: 03/10/1998
ELECTRIC SHOCK & BURN - CONTACT WITH OVERHEAD LINE

Two power line workers were working from an insulated aerial lift, installing armor rods on a 240-kilovolt overhead power line. One of the employees, a supervisor, was using a live-line tool to install the armor rods. The tool contacted the concrete pole and the ground wire hanging from the top of the pole, and current arced from the power line. (The ground wire was connected to the static wire on top of the pole.) The employee holding the live-line tool was electrocuted. His coworker received an electric shock and sustained second- and third-degree burns when the aerial lift burst into flames. He was hospitalized for his injuries.

Keywords: BURN, ELECTRIC ARC, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, LIVE-LINE TOOL, E PTD, ELEC UTILITY WORK, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301023081 Fatality Electric Shock Electrical power installers and repairers
2 301023081 Hospitalized injury Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.