Powered by GoogleTranslate

Inspection Detail

Inspection: 301013686 - Western Resources

Inspection Information - Office: Wichita Area Office

 

Inspection Nr: 301013686
Report ID: 0729700
Date Opened: 06/05/1998

Site Address:
Western Resources
Allen Substation
Humboldt, KS 66748

Mailing Address:
818 S. Kansas Ave, P.O. Box 889, Topeka, KS 66602

Union Status: Union

SIC:4911

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 12/18/1998

Emphasis:

Case Closed: 12/18/1998


Related Activity
Type Activity Nr Safety Health
Accident 101340594
Referral 201340759 Yes

Investigation Summary

Investigation Nr: 201340395
Event: 06/03/1998
BURN - ELECTRICAL FAULT IN REGULATOR

A three-person power line crew was replacing one of a set of three voltage regulators at a substation. The crew consisted of a substation supervisor and two substation electricians. The crew's maintenance supervisor stopped by to observe the operation. The crew obtained switching orders to deenergize the three regulators, which were located on the east side of the substation. The bad regulator was located on the south end of the regulator bank. The crew bypassed the load on the regulators and deenergized them. The crew then replaced the malfunctioning regulator with an Allis-Chalmers regulator (Serial No. 3-3740-00228-9). After the crew visually determined that the controls were in the neutral position as required by the manufacturer, the two electricians took a break. One of them was at the back of the maintenance truck, which was located about 4.3 meters south-southwest of the new regulator. The other electrician was further forward. While these two employees were on break, the substation supervisor closed the bus-side contacts on the three regulators, energizing them. He then closed the load-side contacts. About 5 minutes passed since the supervisor energized the south regulator, but none of the regulators was under full load, as the bypasses were shunting load around the regulators. When the supervisor opened the bypass switch for the new regulator and placed it under load, the regulator failed. The internal pressure in the regulator forced open its lid directly in line with the first electrician, who was sitting on the back of the truck. A large quantity of burning oil from the regulator struck him. The oil also struck the other electrician and the maintenance supervisor, but they were apparently not injured. The second electrician and the substation supervisor extinguished the flames on the injured employee, while the maintenance supervisor summoned emergency medical services with his radio. The injured employee was transported to a local hospital and transferred to a burn center, where he died of complications resulting from second- and third-degree burns over 80 percent of his body.

Keywords: BURN, ELECTRIC ARC, ELECTRICAL, FLAMMABLE LIQUID, POWER LINE WORKER, E PTD, ELEC UTILITY WORK, ELECTRICAL FAULT, ELEC EQUIPMENT--MISC

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 301013686 Fatality Burn/Scald(Heat) Electricians
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.