Inspection: 3010055 - Duke Power Company - Greensboro District

Inspection Information - Office: Nc Department Of Labor - Raleigh

 

Inspection Nr: 3010055
Report ID: 0453710
Date Opened: 08/27/1986

Site Address:
Duke Power Company - Greensboro District
Fairfax Road
Greensboro, NC 27260

Mailing Address:
Post Office Box 33189, Charlotte, NC 28242

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 09/05/1986

Emphasis:

Case Closed: 08/11/1988


Related Activity
Type Activity Nr Safety Health
Accident 360768527
Referral 900775982 Yes
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 1 2 3
Current Violations 1 1
Initial Penalty $0 $0 $0 $0 $0 $0
Current Penalty $490 $0 $0 $0 $0 $490
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Other 19260020 B01 10/27/1986 11/14/1986 $0 $0 $0 11/18/1986 J - ALJ Decision Citation has been deleted.
2. 01001A Serious 19260020 B01 10/27/1986 11/14/1986 $490 $0 $0 J - ALJ Decision  
3. 01001B Serious 19260950 C01 II 10/27/1986 11/14/1986 $0 $0 $0 J - ALJ Decision  
4. 01002 Other 19260950 C01 II 10/27/1986 11/06/1986 $0 $0 $0 11/18/1986 J - ALJ Decision Citation has been deleted.

Investigation Summary

Investigation Nr: 14251771
Event: 08/28/1986
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

AN EMPLOYEE WAS WORKING ALONE ON A TROUBLE CALL AT A RESIDENCE. THE SERVICE DROP FROM THE HOUSE TO THE UTILITY POLE HAD SOME LIMBS ON IT, AND THIS HAD INTERRUPTED POWER TO THE HOUSE. THERE WERE 10 DWELLINGS ON THE DISTRIBUTION LINE FEEDING THE HOUSE. THE DISTRIBUTION TRANSFORMER FOR THE LINE WAS 800 FEET FROM THE HOUSE, AROUND A CORNER. AFTER CLIMBING THE POLE, THE EMPLOYEE APPARENTLY DISCONNECTED THE 120-VOLT SERVICE DROP AND LOWERED IT TO REMOVE THE LIMBS. AFTER HE REMOVED THE LIMBS, HE WENT BACK UP THE POLE TO RECONNECT THE SERVICE DROP. AS HE WAS WORKING ON THE POLE, HE WAS ELECTROCUTED. NO ONE SAW THE ACCIDENT TAKE PLACE, BUT IT WOULD APPEAR FROM THE BURN MARKS THE EMPLOYEE RECEIVED THAT THE BARE END OF A CONDUCTOR CONTACTED THE EMPLOYEE ON THE WRIST. IT WAS ASSUMED THAT THE CONDUCTOR WENT DOWN INSIDE THE GLOVE, AS THE PEOPLE IN THE NEIGHBORHOOD HAD SEEN HIM WEARING HIS GLOVES PREVIOUSLY. NO BLANKET HAD BEEN PLACED OVER THE CABLEVISION OR TELEPHONE CABLE THAT SHARED THE POLE. ADDITIONALLY, THE COMPANY STATED THAT THE EMPLOYEE WAS WORKING AT HIS NORMAL CLASSIFICATION FOR THE TIME OF DAY, BUT THE EMPLOYEE WAS CLASSIFIED AS A METER TECHNICIAN, NOT A LINEMAN.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 3010055 Fatality Electric Shock Misc. electrical & electronic equipment repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.