Inspection Detail
Inspection: 300759354 - Dave Blunk,Dba Edco Drywall Co
Inspection Information - Office: Long Beach District Office
Site Address:
Dave Blunk,Dba Edco Drywall Co
350 Long Beach Blvd
Long Beach, CA 90802
Mailing Address:
7200 Hazard Avenue, Westminster, CA 92683
Union Status: NonUnion
SIC:1742
NAICS: 0
Inspection Type: Accident
Scope: Partial
Advanced Notice: N
Ownership: Private
Safety/Health: Safety
Close Conference: 09/18/2000
Emphasis:
Case Closed: 11/13/2002
| Type | Activity Nr | Safety | Health |
|---|---|---|---|
| Accident | 362404303 |
| Violations/Penalties | Serious | Willful | Repeat | Other | Unclass | Total |
|---|---|---|---|---|---|---|
| Initial Violations | 4 | 2 | 6 | |||
| Current Violations | 3 | 2 | 5 | |||
| Initial Penalty | $21,825 | $0 | $0 | $270 | $0 | $22,095 |
| Current Penalty | $3,025 | $0 | $0 | $270 | $0 | $3,295 |
| FTA Penalty | $0 | $0 | $0 | $0 | $0 | $0 |
| # | Citation ID | Citaton Type | Standard Cited | Issuance Date | Abatement Due Date | Current Penalty | Initial Penalty | FTA Penalty | Contest | Latest Event | Note |
|---|---|---|---|---|---|---|---|---|---|---|---|
| 1. | 01001 | Other | 1646 C | 09/20/2000 | 09/25/2000 | $135 | $135 | $0 | 11/13/2000 | F - Formal Settlement | |
| 2. | 01002 | Other | 25000009 A | 09/20/2000 | 09/25/2000 | $135 | $135 | $0 | 11/13/2000 | F - Formal Settlement | |
| 3. | 02001 | Serious | 23400023 | 09/20/2000 | 09/25/2000 | $275 | $2,475 | $0 | 11/13/2000 | F - Formal Settlement | |
| 4. | 03001 | Serious | 23950045 A03 | 09/20/2000 | 09/25/2000 | $2,475 | $2,475 | $0 | 11/13/2000 | F - Formal Settlement | |
| 5. | 04001 | Serious | 25100058 B | 09/20/2000 | 09/25/2000 | $0 | $2,475 | $0 | 11/13/2000 | F - Formal Settlement | Citation has been deleted. |
| 6. | 05001 | Serious | 25100004 | 09/20/2000 | 09/25/2000 | $275 | $14,400 | $0 | 11/13/2000 | F - Formal Settlement |
Investigation Summary
Two employees were strengthening the ceiling in a small room in a bank that was being renovated. The employees had removed a section of drywall from the ceiling and were working from a rolling scaffold in the area above the ceiling. The employees were using a fluorescent lighting fixture of the type normally found in garages. The two employees had laid the lighting fixture, which had been rigged for portable use, on top of the ceiling. A grounding-type receptacle had been spliced into the power supply cord for the fixture. The fixture had been manufactured with an equipment grounding conductor; however, the plug at the end of the cord had been replaced with a two-pole, nonpolarized plug. One of the circuit conductors inside the metal outlet box was touching the box, and the resulting ground fault had energized the box and cover. One of the employees was electrocuted when he touched the fixture or outlet box.
Keywords: ELECTRICAL, ELECTROCUTED, LIGHTING FIXTURE, E C, GROUND FAULT, EQUIPMENT GROUNDING, ELECTRIC LIGHT--PORT, ELECTRICAL BOX, EQUIPMENT APPROVAL
| # | Inspection | Age | Sex | Degree of Injury | Nature of Injury | Occupation |
|---|---|---|---|---|---|---|
| 1 | 300759354 | Fatality | Electric Shock | Drywall installers |
Translate