Powered by GoogleTranslate

Inspection Detail

Inspection: 300608437 - K & D Construction Company

Inspection Information - Office: Fairview Heights Area Office

 

Inspection Nr: 300608437
Report ID: 0524530
Date Opened: 10/02/1998

Site Address:
K & D Construction Company
Western Aire Subdivision
Marion, IL 62959

Mailing Address:
Highway 45 So., P.O. Box 206, Louisville, IL 62858

Union Status: Union

SIC:1623

NAICS: 0 


Inspection Type: Accident

Scope: Partial

Advanced Notice: N

Ownership: Private

Safety/Health: Safety

Close Conference: 02/08/1999

Emphasis: S:Construction Fatalities

Case Closed: 09/07/1999


Related Activity
Type Activity Nr Safety Health
Accident 361107543
Violation Summary
Violations/Penalties Serious Willful Repeat Other Unclass Total
Initial Violations 4 4
Current Violations 4 4
Initial Penalty $7,400 $0 $0 $0 $0 $7,400
Current Penalty $3,700 $0 $0 $0 $0 $3,700
FTA Penalty $0 $0 $0 $0 $0 $0

Violation Items
# Citation ID Citaton Type Standard Cited Issuance Date Abatement Due Date Current Penalty Initial Penalty FTA Penalty Contest Latest Event Note
1. 01001 Serious 19260453 B02 V 02/10/1999 02/17/1999 $500 $1,000 $0 02/25/1999 J - ALJ Decision  
2. 01002 Serious 19260453 B03 02/10/1999 02/17/1999 $400 $800 $0 02/25/1999 J - ALJ Decision  
3. 01003 Serious 19260950 C02 I 02/10/1999 02/17/1999 $1,400 $2,800 $0 02/25/1999 J - ALJ Decision  
4. 01004 Serious 19260950 D01 V 02/10/1999 02/17/1999 $1,400 $2,800 $0 02/25/1999 J - ALJ Decision  

Investigation Summary

Investigation Nr: 200840387
Event: 10/02/1998
ELECTRIC SHOCK - DIRECT CONTACT WITH OVERHEAD LINE

Two power line workers were installing a new 7200-volt overhead power line. At the time of the accident, they were installing temporary jumpers from an existing power line to the new one. One of the employees was on a newly installed utility pole. His coworker was in an aerial lift assisting him. The new pole was not supporting any energized power lines. However, an existing pole supported an energized power line above the deenergized existing line to which the jumpers were to be connected. The existing pole was about 4.3 meters away from the new pole. The energized line was not protected with insulating equipment. The employee on the pole was using a body belt, positioning strap, and pole climbers and was tied off to the pole. The employee in the aerial lift was holding one end of the jumper as the employee on the pole began connecting the other end. The employee in the aerial lift moved the bucket away from the pole and toward the existing power line. While he was holding onto one end of the jumper and while his coworker was holding onto the other end, the employee in the aerial lift contacted the energized line with his right shoulder. Both employees were electrocuted.

Keywords: ELEC PROTECT EQUIP, OVERHEAD POWER LINE, ELECTRICAL, POWER LINE WORKER, ELECTROCUTED, E PTD, ELEC UTILITY WORK, UTILITY POLE, AERIAL LIFT

Investigated Inspection
# Inspection Age Sex Degree of Injury Nature of Injury Occupation
1 300608437 Fatality Electric Shock Electrical power installers and repairers
2 300608437 Fatality Electric Shock Electrical power installers and repairers
Back to Top

Thank You for Visiting Our Website

You are exiting the Department of Labor's Web server.

The Department of Labor does not endorse, takes no responsibility for, and exercises no control over the linked organization or its views, or contents, nor does it vouch for the accuracy or accessibility of the information contained on the destination server. The Department of Labor also cannot authorize the use of copyrighted materials contained in linked Web sites. Users must request such authorization from the sponsor of the linked Web site. Thank you for visiting our site. Please click the button below to continue.

Close